Special Precautions For R410A

SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R410A UNIT
1) WHAT IS NEW REFRIGERANT R410A?
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant
is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.
2) COMPONENTS
Mixture weight composition
3) CHARACTERISTIC
R410A liquid and vapor components have different compositions when the fluid evaporates or condenses. Hence,
when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the system will change
and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is recommended
that the system should be evacuated thoroughly before recharging with R410A.
When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase.
Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to make
certain that only original composition of R410A is being charged into the system.
POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor.
Extra precaution must be taken not to expose the R410A system too long to moist air.
4) CHECK LIST BEFORE INSTALLATION/SERVICING
Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover
the ends of the tubing prior to installation
Compressor oil
No additional charge of compressor oil is permitted.
Refrigerant
No other refrigerant other that R410A
Tools (size of service port is different from R22 system)
Tools specifically for R410A only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii)
Refrigerant cylinder/charging cylinder
iv)
Vacuum pump c/w adapter
v)
Flare tools
vi)
Refrigerant recovery machine
5) HANDLING AND INSTALLATION GUIDELINES
Like R22 system, the handling and installation of R410A system are closely similar. All precautionary measures; such as
ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and vacuuming
are equally important requirements. However, due to its hydroscopic POE oil, additional precautions must be taken to
ensure optimum and trouble free system operation.
a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.
b)
Ensure that the compressor is not expose to open air for more than the recommended time specified by its manufacturer
(typically less than 10 minutes). Removed the seal plugs only when the compressor is about to be brazed.
c)
The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is more stringent
than R22 system so as to ensure no incompressible gas and moisture in the system.
R32(50%) and R125(50%)
75