Veris DC Current Transducer (CT) Connection Instructions
Analog Sensor Port
*
The applicable output terminal f rom the CT is shown connected to the channel 2 input terminal (Ch2 Signal) on the Analog Sensor Port.
HOBO ZW Series Wireless Data Node; U12 or UX120-006M Logger
HOBO ZW Series Wireless Data Node or U12 Series Data Logger
DC Current Transducer
CABLE-4-20MA
Yellow (+)
Blue (-)
Use appropriate termination
for 4-20mA Output
Distributed by MicroDAQ.com, Ltd.
U30 Connection
HOBO U30 Series Data Logger
DC Current Transducer
for 4-20mA Output*
If available, the channel 1 input terminal (Ch1 Signal) can be used instead.
ZW, U12, and UX120-006M Connection
(ZW shown)
Connect to analog port
CABLE-4-20MA (for 4-20mA output) or
CABLE-ADAP5 (for 0-5VDC output)
AC-SENS-1*
CABLE-ADAP5
(+)
White (+)
(-)
Black (-)
(Red wire not used)
Page 2 of 3
Analog Sensor Port
DC Current Transducer
All wiring
customer-supplied
Analog Sensor Port
for 0-5VDC Output*
DC Current Transducer
DC Current Transducer
LOAD
AC-SENS-1*
(+)
(-)
for 0-5VDC Output
www.MicroDAQ.com
DC
LOAD
DC Current Transducer
AC-SENS-1*
DC
*CAUTION: Polarity is very
important! Before plugging
AC-SENS-1 into AC power,
make sure the correct
polarity lead connections to
device are made as shown!