External Face-and-Bypass Connections

The external face-and-bypass damper sections will
require a field-fabricated duct to direct the bypass air into
the appropriate section. Duct sizing recommendations are
listed in
Table
34.
Table 34. Recommended bypass duct sizes (inches)
Unit size
H
3
16.00
4
18.00
6
18.00
8
18.00
10
18.00
12
22.00
14
22.00
17
22.00
21
28.00
25
28.00
30
28.00
35
45.00
40
45.00
50
45.00
57
47.00
66
48.00
80
56.00
100
56.00
120
56.00
CLCH-SVX07K-EN
W
L
20.00
14.00
33.00
16.00
33.00
16.00
39.00
16.00
50.00
16.00
55.00
20.00
61.00
20.00
61.00
20.00
69.00
26.00
69.00
26.00
82.00
26.00
80.00
36.00
93.00
36.00
106.00
36.00
106.00
40.00
121.00
40.00
121.00
48.00
135.00
48.00
162.00
48.00
When attaching a bypass duct to a downstream fan section
or access section, the section will have a factory-provided
opening. (see
Figure
128,
When bypassing into an access section, remove a panel. It
is not necessary to cut an opening.
Figure 128. External face-and-bypass with duct
configuration designed to bypass air into a
vertical fan section
Fan
Figure 129. External face-and-bypass with duct
configuration designed to bypass air around
one coil
Fan
Coil
Component Installation
Figure
129, and
Figure
130.)
Duct
External
Coil
face-and-bypass
Duct
Access
Coil
External
face-and-bypass
99