Local Mode Signals - Ransburg 80100 Series Service Manual

High voltage controller, hv1 - automatic guns
Table of Contents

Advertisement

LOCAL MODE
(TRIGGER SIGNAL ONLY)
The LOCAL mode is normally used only for
handguns, or very simple automatic gun
systems. Most handguns use an optional air
flow switch (13742-01 or 13742-02) to provide
the trigger signal. The listed flow switches can
be mounted inside the 9060 Controller chassis
via the Air Flow Switch Connector on the side
panel. When the handgun trigger is pressed
and flow starts, the flow switch is activated and
triggers the high voltage. Due to this, only a
single trigger signal input is required to operate
in LOCAL mode.
designed to operate in both REMOTE and
LOCAL modes, it contains all of the wiring
connections for both modes and requires some
minor setting changes to allow operation in
LOCAL mode using only the trigger input
signal.
To operate the Controller in the LOCAL mode,
which uses only the high voltage trigger signal,
perform the following:
Turn the 9060 Controller off, disconnect
1.
it from its AC source, and remove the
fuses.
Open the Controller cabinet door.
2.
W A R N I N G
!
ALWAYS double check that the Con-
troller is unplugged from its AC outlet
before working with any internal wiring.
3. If the flow switch is being used, connect the
ground (green) lead from the flow switch to
the ground screw on the base plate shown
in Figure 13. The trigger signal (blue) lead
should be connected to the trigger signal on
the remote I/O terminal block connector
(Position 5) as shown in Figure 14.
CP-13-05.3
9060 High Voltage Controller - Installation
As the 9060 Controller is
W A R N I N G
!
The 9060 High Voltage Controller is
designed to handle both a sinking or
sourcing trigger input.
DO NOT use a sourcing (User Supplied
24VDC) trigger signal with the 9060 jump-
ers set for sinking (User Supplied Ground)
inputs or vice versa. Sourcing and sink-
ing inputs have different current flow
paths. Using the wrong settings for the
wrong type input can have unexpected
behavior and/or cause damage to the in-
put circuits.
Figure 13: Ground Screw on Base Plate
N O T E
The standard (optional) air flow switch
(13742-01 or 13742-02) used in the 9060
is wired as a sinking switch. When the
flow switch is activated, it connects the
trigger signal input to ground. This re-
quires that the local/remote trigger protec-
tion board be setup to accept a sinking
input. If sourcing inputs are needed, the
flow switch ground wire must be changed
to a 24V DC connection (available on the
terminal blocks).
Ground Screw
24

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

9060 hv1

Table of Contents