NuAire XBOXER XBC Series Installation, Operating And Maintenance Instructions

NuAire XBOXER XBC Series Installation, Operating And Maintenance Instructions

Unit sizes 75 - 85 with ecosmart adapt (trend) control (at)

Advertisement

XBOXER XBC
UNIT SIZES 75 - 85 WITH
ECOSMART ADAPT (TREND) CONTROL (AT)
INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS
ErP
FOR THE
COMPLETE VENTILATION
SOLUTION
COMPLIANT
2016

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XBOXER XBC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NuAire XBOXER XBC Series

  • Page 1 XBOXER XBC UNIT SIZES 75 - 85 WITH ECOSMART ADAPT (TREND) CONTROL (AT) INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS FOR THE COMPLETE VENTILATION SOLUTION COMPLIANT 2016...
  • Page 2: Table Of Contents

    XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) CONTENTS - INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS PAGE 1.0 - 2.0 XBC 75 & 85 Horizontal (AT) Introduction and Access Concepts 3.0 - 4.0 XBC 75 & 85 Horizontal (AT) Dimensions and Weights 5.0 XBC 75 &...
  • Page 3: 2.0 Xbc 75 & 85 Horizontal (At) Introduction And Access Concepts

    XBOXER XBC 75 & 85 (AT Models) Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Installation and Maintenance Directive 2014/35/EU 1.0 XBC 75 & 85 Horizontal Ecosmart Adapt (Trend) (AT) Control Models Code description: XBOXER XBC Ventilation Unit The information contained in this document provides details of XBC 75 - H - LAT - R - WP installation, operation and maintenance for installers and users of...
  • Page 4 Figure 3. Horizontal unit access and configuration. Standard (left hand) unit shown. Intake Counterflow Heat Exchanger G4 Filter Exhaust Extract from room 8mm outside dia. condensate drain. Condensate pump fitted as standard Control with alarm facility Supply to room LPHW or Electric Heater Battery nuaire.co.uk 029 2085 8200...
  • Page 5: 4.0 Xbc 75 & 85 Horizontal (At) Dimensions And Weights

    XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 3.0 XBC 75 & 85 Dimensions and Weights 3.1 XBC 75 & 85 Horizontal (ES and BC) Unit Dimensions (mm) and Weights (kg) Figure 4. Horizontal unit dimensions (mm) and weights (kg). Unit Code Unit Dimensions (mm) Control Dimensions (mm) Unit Weights...
  • Page 6 F7 Bag / G4 Panel with weather roof 2000 XBC75-G4B-HWP G4 Bag with weather roof 2000 1001 XBC85-G4B-HWP G4 Bag with weather roof 2000 1001 XBC75-G4B-HRWP G4 Bag with weather roof 2000 1001 XBC85-G4B-HRWP G4 Bag with weather roof 2000 1001 nuaire.co.uk 029 2085 8200...
  • Page 7 Electric side by side module with base frame for Ecosmart control units (AT) 2000 Above is an indicative list of XBC75 & 85 ancillaries, for further details please contact Nuaire. Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit versions.
  • Page 8: Xbc 75 & 85 Horizontal (At) Spare Parts

    Remove retaining plate & slide filters out to replace slide filters out to replace Blower assemblies. Remove 4 x fixings & slide out to replace IMPORTANT Caution - Blower Weight XBC75 - 18kg XBC85 - 37kg nuaire.co.uk 029 2085 8200...
  • Page 9: 7.0 Xbc 75 & 85 Vertical (At) Introduction And Access Concepts

    XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 6.0 XBC 75 & 85 Vertical Ecosmart Adapt (Trend) (AT) Control Models Code description: XBOXER XBC Ventilation Unit The information contained in this document provides details of installation, operation and maintenance for installers and users of XBC 75 - V - LAT - R - WP the XBOXER XBC75 &...
  • Page 10 Internal control Slide out fans G4 Panel Filter panel access Extract Intake Supply Discharge LPHW or Electric Base Frame 8mm outside dia. condensate drain. Heater Battery (76mm) high Condensate pump fitted as standard with alarm facility. nuaire.co.uk 029 2085 8200...
  • Page 11: 9.0 Xbc 75 & 85 Vertical (At) Dimensions And Weights

    XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 8.0 XBC 75 & 85 Dimensions and Weights 8.1 XBC 75 & 85 Vertical (ES and BC) Unit Dimensions (mm) and Weights (kg) Figure 10. Horizontal unit dimensions (mm) and weights (kg). Unit Code Unit Dimensions (mm) Control Dimensions (mm) Unit Weights...
  • Page 12 F7 Bag / G4 Panel with weather roof 1000 1741 XBC75-G4B-WP G4 Bag with weather roof 1476 XBC85-G4B-WP G4 Bag with weather roof 1000 1741 XBC75-G4B-RWP G4 Bag with weather roof 1476 XBC85-G4B-RWP G4 Bag with weather roof 1000 1741 nuaire.co.uk 029 2085 8200...
  • Page 13 Electric double deck module with base frame for Ecosmart control units (AT) 2000 Above is an indicative list of XBC75 & 85 ancillaries, for further details please contact Nuaire. Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit versions.
  • Page 14: Xbc 75 & 85 Vertical (At) Spare Parts

    Remove retaining plate & slide filters out to replace slide filters out to replace Blower assemblies. Remove 4 x fixings & slide out to replace IMPORTANT Caution - Blower Weight XBC75 - 18kg XBC85 - 37kg nuaire.co.uk 029 2085 8200...
  • Page 15: Delivery Of Equipment

    • That all appropriate risk assessments have been carried out and the If the storage period is to exceed two months, contact Nuaire for required safety measures have been taken. guidance on the appropriate “mothballing” procedures. Do not stack •...
  • Page 16: Commissioning And Setting To Work

    This contact is internally connected to the heat exchanger bypass actuator, and the unit will automatically be placed into bypass mode, preventing further condensate production. Unit operation will otherwise be unaffected. nuaire.co.uk 029 2085 8200...
  • Page 17: Description Of Control - Software Strategy

    XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 14.0 Description of Control - Software Strategy The system incorporates a web enabled Trend IQ422/12/LAN/BAC/230 14.7 Supply Temperature Control controller. While an enable signal is present, this mode modulates heating, cooling & heat exchanger bypass dampers with the aim of the supply air reaching the temperature set-point.
  • Page 18 The upper limit voltage corresponding to the limit of range 0 - 10 VDC CO2-LOOPGAIN CO Loop Gain 0 to -30 -0.5 CO2-LOOPINTEGRAL CO Loop Integral 0 to 30 CO2-LOOPDERIVATIVE CO Loop derivative 0 to 30 nuaire.co.uk 029 2085 8200...
  • Page 19 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) Point Name Description Range Default SUMMERNIGHTFREECOOLACTIVE Set night cooling mode as active Off / On SUMMERNIGHTFREECOOLMINTEMP Night cooling lower cut-off temperature 5°C to 30°C SUMMERNIGHTFREECOOLFANSPEED Night cool fan speed 20 to 100 % STC-COOLLOOPGAIN Supply Temp Control - Cool Loop Gain 0 to -30...
  • Page 20 ECOSMART ADAPT (TREND) CONTROL (AT) 14.11 Sensors and Touch Screens To help you select the appropriate control solution for your application, simply refer to one of the options below. For the full range and technical details, please visit www.nuaire.co.uk Thermistor Temerature Sensors Code: TB/TI/S - For duct or immersion use.
  • Page 21: Electrical Details

    XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 15.0 Electrical Details The electrical wiring must be carried out by competent persons, in accordance with good industry practice and should conform to all governing and statutory bodies i.e. IEE, CIBSE etc. 15.1 Volt Free Contacts Note that the volt free contacts are not fused.
  • Page 22 12 (26, 27) 3RM-2 Relay 1 3RM-2 Relay Module Volt-Free Cool Demand Relay 3RM-2 Relay 2 (HRM Mode) Volt-Free Heat Demand Relay 3RM-2 Relay 3 230V Enable Input 230V Fan Boost Input Volt-Free Healthy Relay 13-14 nuaire.co.uk 029 2085 8200...
  • Page 23 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 15.7 Terminals - Wire Connections Figure 16. This control unit utilises WAGO’s CAGE CLAMP® S terminal blocks, allowing for quick and easy connection. PUSH IN TERMINATION TERMINATION OF FINE-STANDED CONDUCTOR REMOVAL - Stripped solid - Insert an CONDUCTORS conductors, fine-stranded conductors with...
  • Page 24: Connection And Wiring Diagrams

    E) LPHW re-heat drive (LPHW models only) B) Delivery air temperature sensor F) Bypass damper drive C) Extract air temperature sensor G) Condensate pump alarm D) Re-heater trip (electric heater models only) H) Fresh air temperature Extract fan (drive & health) nuaire.co.uk 029 2085 8200...
  • Page 25 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.3 Basic Connection Diagram 22. 01. 18. Leaflet Number 671730...
  • Page 26 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.4 Physical Layout - Horizontal Unit nuaire.co.uk 029 2085 8200...
  • Page 27 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 22. 01. 18. Leaflet Number 671730...
  • Page 28 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.5 Physical Layout - Vertical Unit nuaire.co.uk 029 2085 8200...
  • Page 29 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 22. 01. 18. Leaflet Number 671730...
  • Page 30 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.6 XBC 75 & 85 - No Heater / LPHW nuaire.co.uk 029 2085 8200...
  • Page 31 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 22. 01. 18. Leaflet Number 671730...
  • Page 32 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.7 XBC 75 & 85 - Electric Heater nuaire.co.uk 029 2085 8200...
  • Page 33 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 22. 01. 18. Leaflet Number 671730...
  • Page 34 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.8 XBC 75 & 85 Frost Coil Wiring (LPHW Heater) nuaire.co.uk 029 2085 8200...
  • Page 35 XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT) 16.9 XBC 75 & 85 Frost Coil Wiring (Electric Heater) 22. 01. 18. Leaflet Number 671730...
  • Page 36: 19.0 Maintenance & Warranty

    Clause 14 of our Conditions of Sale. Customers purchasing from service visits. outside of the UK should contact Nuaire International Sales office for further details. Note: The unit application may require particular attention to this item –...
  • Page 37 GENERAL In addition to the particular requirements given for the individual product, the following The equipment referred to in this Declaration of Incorporation is supplied by Nuaire to general requirements should be noted. be assembled into a ventilation system which may or may not include additional Where access to any part of equipment which moves, or can become electrically live are components.
  • Page 38 CF83 1NA +44 (0)29 2085 8200 +44 (0)29 2085 8222 info@nuaire.co.uk www.nuaire.co.uk As part of our policy of continuous product development Nuaire reserves the right to alter specifications without prior notice. Telephone calls may be recorded for quality and training purposes.