17.0 Maintenance
It is recommended that PPE is always used during the maintenance of
Air Handling Equipment – gloves, eye shields and respiratory mask.
IMPORTANT
Isolation - Before commencing work, make sure that the unit and
Nuaire control are electrically isolated from the mains supply.
In some Ecosmart units and in some third party controls, variable speed
drives (inverters) are used to provide fan speed control. After the fan is
isolated, allow at least 5 minutes for the capacitors in the inverter to
discharge before commencing any work on the unit.
17.1 Dampers
Regularly check that the damper blades move freely.
17.2 Filters (4 x G4 Fitted as standard)
Disposable filters should be changed when an appropriate pressure
drop is achieved.
17.3 Heating Coils
Coils should have their finned surface examined for accumulation of
dirt, lint and biological contaminants or similar.
If necessary, wash down affected areas with a mild detergent solution
and a soft brush. Care should be taken not to damage the finned
surface and any cleaning fluids should be rinsed away with water. A
compressed air line may be used to blow out any solids between fins.
Do not probe the coil fin block with metal objects as damage may
cause leaks.
Drain lines should be checked to ensure that they are unobstructed and
free draining.
Drain pans should be flushed out periodically to remove contamination.
Note: The unit application may require particular attention to this
item – Check with Building Management personnel for details.
17.4 Counterflow Plate Heat Exchanger
The heat exchanger block is normally protected from dust and
contamination by upstream pre-filters. It is possible to clean the unit
with compressed air in the case of dust deposits or by spraying with a
mild detergent solution for grease deposits. Solvents, strong alkaline,
acidic or any products that may be aggressive to aluminium should not
be used. Do not use cleaning water over a temperature of 50 °C.
Drain lines should be checked to ensure that they are unobstructed and
free draining. Traps should be checked that they are fully primed and
functioning.
Drain pans should be flushed out periodically to remove contamination,
and chemical treatments may be used to provide protection between
service visits.
Note: The unit application may require particular attention to this
item – Check with Building Management personnel for details.
Telephone 02920 858 400
aftersales@nuaire.co.uk
nuaire.co.uk
029 2085 8200
17.5 Fans and Motors
Fan bearings should be manually checked at regular intervals for
condition. Standard fan bearings are supplied as 'sealed for life' and
have an anticipated life of 40,000 hours.
Motors have an enclosed bearing housing and are pre-greased for life.
Check all fixings are secure.
17.6 General
Inspect all internal and external surfaces to check for corrosion or
peeling of painted surfaces.
Thoroughly clean affected areas with a wire brush, apply a coat of zinc
rich primer or similar, and re-touch with suitable finishing paint. Ensure
tightness of all nuts, bolts, and fixings.
Check all components for general condition.
18.0 Service Schedule
Typical–will depend on site conditions
G4 FILTERS
F7 FILTERS
DAMPERS
DAMPER ACTUATORS
VENT WATER COILS
COIL FINNED SURFACES
CHECK DRAIN LINES + DRIP TRAY
CHECK DRAIN PANS
NUTS, BOLTS, FIXINGS SECURE
FAN BEARINGS
ELECTRIC HEATERS
ELECTRICAL WIRING
FAN IMPELLER
GENERAL
19.0 Warranty
5 year warranty on Ecosmart models for peace of mind. The warranty
starts from the day of delivery and includes parts and labour for the first
year. The remaining period covers replacement parts only.
This warranty is void if the equipment is modified without
authorisation, is incorrectly applied, disassembled misused or not
installed commissioned and maintained in accordance with the details
contained in this manual and general good practice.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Conditions of Sale. Customers purchasing from
outside of the UK should contact Nuaire International Sales office for
further details.

20.0 After Sales Enquiries

For technical assistance or further product information, including spare
parts and replacement components, please contact the After Sales
Department.
6 MONTHS
12 MONTHS
P
Por
P
P
P
P
P
P
P
Building
P
Schedule?
P
P
P
P
P
P

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents