Auto formula select time:
The auto formula select time is used with micro mode to
establish a time ―increment‖ for selecting formulas. The
signal duration will be divided by the number selected to
choose the formula. The available signal time
increments (in seconds) are 1—5. Pump 6 is the signal
that is used for auto formula select.
Example: If the auto formula select signal time is set for
2, a 20 second signal from the washer would choose
formula 10 on the dispenser.
(1) Enter the access code if you do not already have
access to the system.
(2) Select pump A, and formula A.
(3) Use / to input the auto formula select time 1 – 5,
then ENTER.
NOTE: A setting of 000 means that the auto
formula select function is turned off (disabled).
DISABLE
000
AFS TIME
(4) The display will flash briefly, indicating that the auto
formula select time was accepted.
NOTE: If AFS is enabled, the system is limited to 5
chemical pumps (as pump 6 is dedicated for AFS
signal).
Page 14 of 20
Auto formula select mode:
MICRO: For use with microprocessor controlled
washers that can send a signal of exact duration to the
unit. The controller interprets the duration of the signal
as the formula number requested, based on the auto
formula select time setting explained in the next menu
selection.
CHART: For use with card-reader type machines. Uses
a combination of signals to pick the formula in a ―binary‖
numbering format.
(1) Enter the access code if you do not already have
access to the system.
(2) Select pump F, and formula A.
(3) Use / to select 000 (micro) or 001 (chart) then
ENTER.
001
(4) The display will flash briefly, indicating that the auto
formula select mode was accepted.
MICRO
000
CHART
001