Figure 6. Fisher LCP100 Local Control Panel Dimensions
E1077‐1
Pre‐Setup Testing
Before connecting the LCP100 to the process, conduct the following tests on the LCP100 connected to the
DVC6200 SIS.
Successful Partial Stroke Test
1. Press the Valve Test (bottom) pushbutton for more than 3 seconds (but less than 10 seconds).
2. Observe that the green light starts flashing when the valve starts moving.
3. Observe that the valve moves no more than the configured partial stroke test travel limit.
4. Observe that the valve returns to the normal operating position and the green light comes on solid.
Manually Aborted Partial Stroke Test
1. Press the Valve Test (bottom) pushbutton for more than 3 seconds (but less than 10 seconds).
2. Observe that the green light starts flashing when the valve starts moving.
3. Before the valve reaches the travel limit of the configured partial stroke test, press the Valve Test pushbutton, or
the pushbutton next to the green light.
4. Observe that the valve immediately returns to the normal operating position and the green light comes on solid.