LCP100 Local Control Panel
August 2012
If the LCP100 is connected to a DVC6200 SIS in a zone 1 explosion proof "d" environment, there must be a conduit seal
installed between the DVC6200 SIS and the LCP100 in order to maintain the explosion proof integrity of the DVC6200
SIS. Refer to figures 9 and 10.
The LCP100 cannot be connected to a DVC6200 SIS that is part of a zone 0 or zone 1 intrinsically safe "i" installation.
When installing in a hazardous area, use zone 1 approved wiring practices.
CSA
Ex em IIC, IP66
Rated 30 VDC maximum; 100 mA maximum; temperature code rating T4, ambient temperature range -40_C to 65_C
Special Conditions of Use
1. Install in an area that has a low risk of mechanical damage.
2. Install the cover, tightening the screws evenly in a criss‐cross pattern such as the one indicated in figure 2 to help
ensure the cover is properly installed.
Figure 2. Proper Cover Installation
NOTE: TIGHTEN THE SCREWS IN A CRISS‐CROSS PATTERN TO
HELP ENSURE PROPER COVER INSTALLATION
ATEX / IECEx
II 2G Ex e mb [ib] IIC T4 Gb Ta = -40 _C to +65_C, IP66
ATEX:
IECEX: Ex e mb [ib] IIC T4 Gb Ta = -40 _C to +65_C, IP66
Standards Used for Certification
IEC 60079-0:2004
IEC 60079-0:2007
IEC 60079-7:2006
Special Conditions for Safe Use
1. The loop + and 24 VDC circuits shall not be simultaneously connected.
4
IEC 60079-11:2006
IEC 60079-18:2004
EN 60079-0:2006
EN 60079-7:2007
EN 60079-11:2007
EN 60079-18:2004
Instruction Manual
D103272X012