VIII. Initial Installation Data
The following initial installation data should be maintained on site:
Date and Initial open circuit voltage of unit(s) at time of delivery to the site.
Freshening charge records, if performed.
Initial torque value used for connections.
Overall system float voltage across battery terminals.
Individual unit float voltage.
Internal Ohmic value of each unit.
Connection resistances.
Float current.
IX. Periodic Maintenance
These VRLA batteries are maintenance free with respect to the electrolyte. However, the charging voltage,
temperature, performance and connection resistances must be periodically monitored and any necessary
corrective actions taken if irregular values are observed to assure reliable standby power when required.

Quarterly Inspection

Measure and record the system total float charging voltage at the battery terminals
Record the charger on charge output current and voltage
Record the ambient temperature and condition of ventilation equipment
Visually inspect the batteries and rack for general appearance, cleanliness or any irregularity.
If gas tubing provisions are utilized, check for any obstructions in the tubing which would prevent
the free flow of gases thru the exit point.

Semiannual Inspection

Repeat the quarterly checks
Record the on charge voltage of each unit
Optionally perform and record Ohmic checks for trending purposes
Yearly and Initial Inspection
Repeat the semiannual checks
Inspect all connections to ensure integrity.
1400 Union Meeting Road
P.O. Box 3053 • Blue Bell, PA 19422-0858
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630
customersvc@cdtechno.com
www.cdtechno.com
Any data, descriptions or specifications presented herein are subject to revision by
C&D Technologies, Inc. without notice. While such information is believed to be accurate
as indicated herein, C&D Technologies, Inc. makes no warranty and hereby disclaims all
warranties, express or implied, with regard to the accuracy or completeness of such
information. Further, because the product(s) featured herein may be used under
conditions beyond its control, C&D Technologies, Inc. hereby disclaims all warranties,
either express or implied, concerning the fitness or suitability of such product(s) for any
particular use or in any specific application or arising from any course of dealing or usage
of trade. The user is solely responsible for determining the suitability of the product(s)
featured herein for user's intended purpose and in user's specific application.
Copyright 2014 C&D TECHNOLOGIES, INC.
Printed in U.S.A.
RS-2046 0514/CD

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TEL Series and is the answer not in the manual?

This manual is also suitable for:

Tel12-105fnsgTel12-105fnsTel12-115fnTel12-115fngTel12-145fwTel12-155f ... Show all

Table of Contents