Page 1
RS02046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER’S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES. For additional information: www.cdtechno.com Technical-Warranty Assistance, contact: C&D Technologies, Inc. 1400 Union Meeting Road / PO Box 3053 / Blue Bell, PA 19422-0858...
Page 2
General: The purpose of this manual is to inform installers how to receive, install and maintain C&D Technologies front access batteries. Battery Description: The Valve Regulated Lead Acid (VRLA) battery is a minimal maintenance system utilizing an oxygen recombination cycle to minimize gassing and eliminate electrolyte maintenance. The dilute sulfuric acid electrolyte is immobilized by absorbent glass mat (AGM) separators.
Page 3
Code (NEC) and other applicable building codes. Please note that for sealed cabinets with VRLA gas removal provisions, the C&D TEL Series batteries with gas collection (G suffix) and the optional tubing kit can be utilized (see Diagram in Section V of this document) •...
Page 4
III. Storage Instructions Store batteries in a clean, dry, cool area away from radiant heat sources. Recharge batteries in storage at least every 6 months or before their OCV declines to 12.48 VDC. Follow instructions as outlined in Section VI. Freshening Charge.
Page 5
Series -48VDC connection of individual front access batteries Step 1. If installing in a multiple tier rack or cabinet arrangement, always begin with the lowest shelf, string A, place each the individual front access batteries on the shelf (typically 4 per level) with approximately 1/2 inch spacing between the individual units.
Page 6
Series +24VDC connection of individual front access batteries Step If installing in a multiple tier rack or cabinet arrangement, always begin with the lowest shelf, string A & B, place each the individual front access batteries on the shelf (typically 4 per level) with approximately 1/2 inch spacing between the individual units.
Page 7
V. Optional Gas Collection System Installation (tubing kit PN 15028596) TEL Series Models with ‘G’ in the product suffix (i.e. TEL12-105FNSG) include a gas collection system feature which allows the hydrogen and oxygen gases that may vent from the battery to be directed to a specific cabinet exit location by the installation of 6mm or ¼”...
Page 8
VIII. Initial Installation Data The following initial installation data should be maintained on site: • Date and Initial open circuit voltage of unit(s) at time of delivery to the site. • Freshening charge records, if performed. • Initial torque value used for connections. •...