Electrical Data - York YCUL0016 User Manual

Air-cooled scroll condensing units
Table of Contents

Advertisement

Electrical Data

(One Field Provided Power Supply to the condensing unit. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Disconnect Switch
SINGLE POINT FIELD SUPPLIED WIRING
MIN
MODEL
N/F
VOLT HZ MCA
1
YCUL
DISC
SW
200
60
71
100
230
60
70
100
380
60
42
60
0016
460
60
35
60
575
60
28
30
200
60
92
100
230
60
91
100
380
60
55
60
0026
460
60
46
60
575
60
37
60
200
60
107
150
230
60
106
150
380
60
64
100
0030
460
60
53
60
575
60
43
60
200
60
124
150
230
60
124
150
380
60
75
100
0036
460
60
62
100
575
60
50
60
200
60
147
200
230
60
146
200
380
60
88
100
0040
460
60
73
100
575
60
59
100
UNIT VOLTAGE
UNIT VOLTAGE
MODELS w/o
CONTROL TRANS
MODELS w/
CONTROL TRANS
A. Minimum #14 AWG, 75°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
VOLTAGE CODE
-17
-28
-40
-46
-58
YORK INTERNATIONAL
YCUL0016 - YCUL0040
SINGLE POINT POWER SUPPLY CONNECTIONS (See Fig. 1)
(optional) or Circuit Breaker (optional).)
INCOMING (LUGS) WIRE RANGE
D.E. FUSE
CKT. BKR.
5
TERMINAL
MIN
MAX
MIN
MAX
BLOCK (std)
3
4
2
80
90
80
90
# 10 - # 1
80
90
80
90
# 10 - # 1
50
50
50
50
# 10 - # 1
40
45
40
45
# 10 - # 1
35
35
35
35
# 10 - # 1
100
110
100
110
# 10 - # 1
100
110
100
110
# 10 - # 1
60
70
60
70
# 10 - # 1
50
60
50
60
# 10 - # 1
40
45
40
45
# 10 - # 1
125
125
125
125
# 10 - # 1
125
125
125
125
# 10 - # 1
70
80
70
80
# 10 - # 1
60
70
60
70
# 10 - # 1
50
50
50
50
# 10 - # 1
150
150
150
150
# 10 - 3/0
150
150
150
150
# 10 - 3/0
90
90
90
90
# 10 - # 1
70
70
70
70
# 10 - # 1
60
60
60
60
# 10 - # 1
175
175
175
175
# 10 - 3/0
175
175
175
175
# 10 - 3/0
100
110
100
110
# 10 - # 1
80
90
80
90
# 10 - # 1
70
70
70
70
# 10 - # 1
CONTROL POWER
115-1-60/50
-17
200-1-60
-28
230-1-60
-40
380-1-60
-46
460-1-60
-58
575-1-60
VOLTAGE RANGE
UNIT POWER
200-3-60
230-3-60
380/415-3-60
460-3-60
575-3-60
SYSTEM #1 COMPRESSOR & FAN
6
COMPR. #1
NF DISC.
CIRCUIT
SWITCH
BREAKER
RLA LRA
(opt)
(opt)
# 14 - 1/0
# 14 - 1/0
24.0
189
# 14 - 1/0
# 14 - 1/0
24.0
189
# 14 - 2
# 14 - 2
14.4
112
# 14 - 2
# 14 - 2
12.0
99
# 14 - 2
# 14 - 2
9.6
74
# 14 - 1/0
# 14 - 1/0
33.2
278
# 14 - 1/0
# 14 - 1/0
33.2
278
# 14 - 2
# 14 - 2
19.9
151
# 14 - 2
# 14 - 2
16.6
127
# 14 - 2
# 14 - 2
13.3
100
# 2 - 4/0
# 2 - 4/0
40.0
350
# 2 - 4/0
# 2 - 4/0
40.0
350
# 14 - 1/0
# 14 - 1/0
24.0
195
# 14 - 2
# 14 - 2
19.9
167
# 14 - 2
# 14 - 2
16.0
125
# 2 - 4/0
# 2 - 4/0
47.8
425
# 2 - 4/0
# 2 - 4/0
47.8
425
# 14 - 1/0
# 14 - 1/0
28.7
239
# 14 - 1/0
# 14 - 1/0
23.9
198
# 14 - 2
# 14 - 2
19.1
148
# 3 - 300
# 3 - 300
40.0
350
# 3 - 300
# 3 - 300
40.0
350
# 14 - 1/0
# 14 - 1/0
24.0
195
# 14 - 1/0
# 14 - 1/0
19.9
167
# 14 - 1/0
# 14 - 1/0
16.0
125
OVER CURRENT PROTECTION,
MCA
NOTE A
MIN
15A
10A
15A
10A
15A
10A
15A
10A
15A
10A
15A
10A
MIN.
180
207
342
414
517
FORM 150.63-EG1
COMPR. #2
COMPR. #3
FANS
RLA
LRA
RLA
LRA QTY
24.0
189
2
24.0
189
2
14.4
112
2
12.0
99
2
9.6
74
2
33.2
278
2
33.2
278
2
19.9
151
2
16.6
127
2
13.3
100
2
40.0
350
2
40.0
350
2
24.0
195
2
19.9
167
2
16.0
125
2
47.8
425
2
47.8
425
2
28.7
239
—-
2
23.9
198
2
19.1
148
2
40.0
350
40.0
350
2
40.0
350
40.0
350
2
24.0
195
24.0
195
2
19.9
167
19.9
167
2
16.0
125
16.0
125
2
SEE NOTE B
NFDISC Sw
MAX
15A
30 A / 240V
15A
30 A / 240V
15A
30 A / 240V
15A
30 A / 480V
15A
30 A / 480V
15A
30 A / 600V
MAX.
220
253
440
506
633
FLA
(EA)
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
8.2
7.8
4.8
4.0
3.1
103