Ratings -
HFC-407C (English Units)
YCUL0040EB
SST
75°F
(°F)
TONS
KW
EER
TONS
34.5
31.9
11.9
35.0
35.8
32.3
12.2
37.0
37.2
32.7
12.6
39.0
38.6
33.0
12.9
41.0
40.1
33.4
13.3
43.0
41.6
33.8
13.6
45.0
43.2
34.3
14.0
47.0
44.8
34.7
14.3
49.0
46.4
35.2
14.7
51.0
48.1
35.7
15.0
53.0
49.8
36.2
15.3
55.0
YCUL0046EB
SST
75°F
(°F)
TONS
KW
EER
TONS
37.8
31.8
12.1
35.0
39.4
32.0
12.6
37.0
40.6
32.8
12.7
39.0
42.7
32.2
13.5
41.0
44.4
32.4
14.0
43.0
46.2
32.5
14.5
45.0
47.8
33.0
14.9
47.0
49.7
33.1
15.4
49.0
51.6
33.2
16.0
51.0
53.6
33.4
16.5
53.0
55.6
33.6
17.0
55.0
YCUL0050EB
SST
75°F
(°F)
TONS
KW
EER
TONS
42.3
37.5
11.8
35.0
44.0
37.8
12.2
37.0
45.8
38.0
12.6
39.0
47.6
38.3
13.0
41.0
49.5
38.6
13.4
43.0
51.4
39.1
13.8
45.0
53.4
39.4
14.3
47.0
55.5
39.7
14.7
49.0
57.6
40.0
15.1
51.0
59.8
40.4
15.6
53.0
62.0
40.8
16.0
55.0
YCUL0056EB
SST
75°F
(°F)
TONS
KW
EER
TONS
46.8
41.9
11.8
35.0
48.7
42.2
12.2
37.0
50.7
42.6
12.6
39.0
52.7
43.0
13.0
41.0
54.8
43.4
13.4
43.0
56.9
43.9
13.8
45.0
59.1
44.4
14.2
47.0
61.4
44.9
14.6
49.0
63.7
45.4
15.0
51.0
66.0
46.0
15.4
53.0
68.5
46.6
15.8
55.0
NOTES:
1. SST = Saturated Suction Temperature
2. kW = Compressors Input Power
3. EER = Condensing Unit EER (includes power from compressors, fans and the control panel)
36
AIR TEMPERATURE ON CONDENSER (°F)
80°F
85°F
KW
EER
TONS
KW
33.4
33.8
10.9
32.4
35.8
34.7
34.2
11.3
33.6
36.2
36.1
34.5
11.6
35.0
36.6
37.5
34.9
11.9
36.3
37.0
38.9
35.4
12.2
37.7
37.4
40.4
35.8
12.6
39.1
37.8
41.9
36.2
12.9
40.6
38.2
43.4
36.7
13.2
42.1
38.7
45.0
37.1
13.5
43.7
39.2
46.7
37.6
13.9
45.2
39.7
48.3
38.1
14.2
46.9
40.2
AIR TEMPERATURE ON CONDENSER (°F)
80°F
85°F
KW
EER
TONS
KW
36.7
33.8
11.2
35.6
35.9
38.3
33.9
11.6
36.5
37.2
39.8
34.1
12.0
38.7
36.2
41.5
34.2
12.5
40.3
36.3
43.1
34.4
12.9
41.9
36.5
44.9
34.5
13.4
43.6
36.7
46.4
35.0
13.7
45.1
37.2
48.3
35.1
14.2
46.9
37.4
50.2
35.3
14.7
48.7
37.5
52.1
35.4
15.2
50.6
37.6
54.1
35.6
15.8
52.6
37.8
AIR TEMPERATURE ON CONDENSER (°F)
80°F
85°F
KW
EER
TONS
KW
41.0
39.8
10.8
39.8
42.3
42.7
40.0
11.2
41.4
42.5
44.5
40.3
11.6
43.1
42.8
46.3
40.6
12.0
44.9
43.0
48.1
40.9
12.4
46.7
43.3
50.0
41.2
12.8
48.5
43.6
51.9
41.7
13.2
50.3
44.2
53.9
42.0
13.6
52.3
44.5
56.0
42.3
14.0
54.3
44.8
58.1
42.7
14.4
56.4
45.2
60.3
43.1
14.9
58.5
45.6
AIR TEMPERATURE ON CONDENSER (°F)
80°F
85°F
KW
EER
TONS
KW
45.4
44.4
10.9
44.0
47.1
47.3
44.7
11.3
45.8
47.4
49.2
45.1
11.6
47.7
47.8
51.2
45.5
12.0
49.6
48.1
53.2
45.9
12.4
51.6
48.6
55.3
46.3
12.8
53.6
49.0
57.4
46.8
13.1
55.7
49.5
59.6
47.3
13.5
57.8
50.0
61.8
47.9
13.9
60.0
50.5
64.2
48.4
14.3
62.3
51.1
66.5
49.0
14.6
64.6
51.7
90°F
EER
TONS
KW
EER
TONS
10.0
31.3
38.0
9.2
30.2
10.4
32.5
38.3
9.5
31.4
10.7
33.8
38.7
9.8
32.7
11.0
35.1
39.1
10.1
33.9
11.3
36.5
39.5
10.3
35.3
11.6
37.9
40.0
10.6
36.6
11.9
39.3
40.4
10.9
38.0
12.2
40.8
40.9
11.2
39.4
12.5
42.3
41.4
11.5
40.9
12.8
43.9
41.9
11.8
42.4
13.1
45.4
42.4
12.1
44.0
90°F
EER
TONS
KW
EER
TONS
10.3
34.5
38.2
9.5
33.4
10.2
35.4
39.5
9.4
34.8
11.1
37.5
38.5
10.2
36.3
11.5
39.0
38.6
10.6
37.8
11.9
40.6
38.8
11.0
39.3
12.4
42.2
39.0
11.4
40.9
12.6
43.9
39.2
11.8
42.5
13.1
45.5
39.7
12.0
44.1
13.6
47.3
39.8
12.5
45.8
14.1
49.1
40.0
12.9
47.6
14.5
51.0
40.2
13.4
49.5
90°F
EER
TONS
KW
EER
TONS
10.0
38.5
44.9
9.2
37.2
10.3
40.1
45.1
9.5
38.8
10.7
41.8
45.4
9.8
40.4
11.1
43.5
45.6
10.2
42.0
11.4
45.2
45.9
10.5
43.8
11.8
47.0
46.3
10.9
45.5
12.1
48.8
46.8
11.2
47.3
12.5
50.7
47.1
11.5
49.1
12.9
52.6
47.5
11.9
51.0
13.3
54.7
47.8
12.3
53.0
13.7
56.7
48.2
12.6
55.0
90°F
EER
TONS
KW
EER
TONS
10.0
42.5
49.9
9.2
41.1
10.4
44.3
50.2
9.5
42.8
10.7
46.1
50.6
9.9
44.6
11.1
48.0
51.0
10.2
46.4
11.4
49.9
51.4
10.5
48.3
11.8
51.9
51.9
10.8
50.2
12.1
53.9
52.4
11.2
52.2
12.5
56.0
52.9
11.5
54.2
12.8
58.1
53.4
11.8
56.3
13.2
60.3
54.0
12.2
58.4
13.5
62.6
54.6
12.5
60.6
95°F
100°F
KW
EER
TONS
KW
EER
40.2
8.4
29.1
42.5
7.7
40.6
8.7
30.3
42.9
7.9
41.0
8.9
31.5
43.4
8.2
41.4
9.2
32.7
43.8
8.4
41.8
9.5
34.0
44.2
8.7
42.3
9.7
35.4
44.7
8.9
42.8
10.0
36.7
45.2
9.2
43.2
10.3
38.1
45.7
9.4
43.7
10.5
39.5
46.2
9.7
44.3
10.8
41.0
46.8
9.9
44.8
11.1
42.5
47.3
10.2
95°F
100°F
KW
EER
TONS
KW
EER
40.6
8.7
32.3
43.1
7.9
40.7
9.0
33.6
43.2
8.3
40.9
9.4
35.1
43.4
8.6
41.0
9.7
36.5
43.6
8.9
41.2
10.1
38.1
43.8
9.2
41.4
10.5
39.6
44.0
9.6
41.8
10.8
41.2
44.2
9.9
42.2
11.1
42.6
44.8
10.1
42.4
11.5
44.4
45.0
10.5
42.5
11.9
46.2
45.2
10.9
42.7
12.3
47.9
45.4
11.3
95°F
100°F
KW
EER
TONS
KW
EER
47.6
8.4
35.9
50.5
7.7
47.9
8.7
37.4
50.7
8.0
48.1
9.0
39.0
51.0
8.3
48.4
9.3
40.6
51.3
8.6
48.7
9.7
42.3
51.7
8.9
49.1
10.0
44.0
52.0
9.2
49.4
10.3
45.8
52.4
9.5
49.9
10.6
47.4
53.0
9.7
50.3
10.9
49.3
53.3
10.0
50.7
11.3
51.2
53.7
10.4
51.1
11.6
53.2
54.1
10.7
95°F
100°F
KW
EER
TONS
KW
EER
52.8
8.4
39.6
56.0
7.7
53.2
8.7
41.3
56.3
8.0
53.6
9.0
43.0
56.8
8.3
54.0
9.3
44.8
57.2
8.6
54.5
9.6
46.6
57.7
8.8
55.0
9.9
48.5
58.1
9.1
55.4
10.3
50.4
58.6
9.4
55.9
10.6
52.4
59.2
9.7
56.5
10.9
54.4
59.8
10.0
57.1
11.2
56.5
60.3
10.3
57.7
11.5
58.6
61.0
10.6