Electrical Data - Outdoor Unit; Electrical Data - York YJ-40 Installation Manual

Hide thumbs Also See for YJ-40:
Table of Contents

Advertisement

Electrical Data

Table 5: Electrical Data - Outdoor Unit
Model
Power
Supply
208/230-3-60
YJ-30
460-3-60
575-3-60
208/230-3-60
YJ-40
460-3-60
575-3-60
208/230-3-60
YJ-50
460-3-60
575-3-60
1. Maximum fuse or maximum circuit breaker (HACR type per NEC).
2. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
Johnson Controls Unitary Products
Compressors
RLA
MCC
Qty
(each)
(each)
(each)
4
25.0
39
4
12.2
19
4
9.0
14
4
30.1
47
4
16.7
26
4
12.2
19
4
48.1
75
4
18.6
29
4
14.7
23
Outdoor Fan Motor
LRA
Power
Supply
164
208/230-3-60
1 1/2
100
460-3-60
1 1/2
78
575-3-60
1 1/2
225
208/230-3-60
1 1/2
114
460-3-60
1 1/2
80
575-3-60
1 1/2
245
208/230-3-60
1 1/2
125
460-3-60
1 1/2
100
575-3-60
1 1/2
Minimum
Circuit
FLA
HP
Qty
Ampacity
(each)
4
5.8
129.5
4
2.9
63.5
4
2.2
47.1
4
5.8
151.1
4
2.9
82.6
4
2.2
60.7
4
5.8
227.6
4
2.9
90.7
4
2.2
71.3
579884-BIM-A-0710
Maximum
Fuse Size
1
2
(A)
150
70
50
175
90
70
250
100
80
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Yj-30Yj-50

Table of Contents