Mitsubishi Electric MELSEC-Q QE81WH4W User Manual page 56

Energy measuring module
Table of Contents

Advertisement

6 Buffer memory
6.3.8 Average current (Un \ G218, 219)
Stores the average current.
For procedure for storing the average current, refer to section 4.2.1 (2).
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range:0 to 99999990 (0 to 99999.990 A)
*For restrictions for measured data including resolution and measuring range, refer to section
4.2.1.
(b) Unit
-3
×10
A
(c) Update timing
It will be updated every measuring cycle (250 ms).
6.3.9 Maximum value of electric current demand (Un \ G220,221), minimum value of electric current
demand (Un \ G226,227)
Stores the max./min. values of the electric current demand among phases.
For procedure for storing the max./min. the electric current demand, refer to section 4.2.1 (2).
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range: 0 to 99999990 (0 to 99999.990 A)
*For restrictions for measured data including resolution and measuring range, refer to section
4.2.1.
(b) Unit
-3
×10
A
(c) Update timing
It will be updated every measuring cycle (250 ms) if it exceeds the current max. value or goes
under the current min. value.
*Unit is fixed.
*Unit is fixed.
6 – 17
QE81WH4W

Advertisement

Table of Contents
loading