6 Buffer memory
(2) Default value
Input voltage (Un¥G1) is set to 63.5/110 V (101).
Primary voltage of VT (Un¥G5) is set to 0.
Secondary voltage of VT (Un¥G6) is set to 0.
6.2.3 Primary current (Un \ G2) , Primary current of CT (Un \ G7)
・Primary current (Un\G2): set the primary current of the target electric circuit.
・Primary current of CT (Un\G7): when use for primary current of current transformer that is not in the
(1) Setting procedure
(a) Set the primary current and primary current of CT in the buffer memory. Setting range is as
follows: Please choose the settings to match the current sensor to be used.
When set other than "1 to 5, 501 to 536" the value of this setting, set to "0: any setting" this
setting, and set primary current of CT (Un¥G7).
When the value of this setup is set as "1 to 5, 501 to 536", primary current of CT is disabled.
Primary current (Un\G2)
Setting value
0
1
2
3
4
5
501
502
503
504
505
506
507
508
509
510
511
512
513
514
primary current (Un\G2) setting, set the current of the primary side
of current transformer.
Primary current of CT
Description
Any setting
50A
100A
250A
400A
600A
5/5A
6/5A
7.5/5A
8/5A
10/5A
(However, this setting is
12/5A
15/5A
20/5A
25/5A
30/5A
40/5A
50/5A
60/5A
75/5A
6 – 7
Current sensor
(Un\G7)
1 - 6600
EMU2-CT5-4W
EMU-CT50
EMU-CT100
EMU-CT250
EMU-CT400
EMU-CT600
0 – 6600
disabled)
EMU2-CT5-4W
QE81WH4W