Cooling Capacities For Wr180 (Alternate Reheat Mode) - York SUNLINE MAGNADRY WR240 Technical Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MAGNADRY WR240:
Table of Contents

Advertisement

TABLE 7: COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE)
Air on Evaporator Coil
WB
CFM
(°F)
67
4500
62
57
67
5250
62
57
67
6000
62
57
67
6750
62
57
67
7500
62
57
67
4500
62
57
67
5250
62
57
67
6000
62
57
67
6750
62
57
67
7500
62
57
67
4500
62
57
67
5250
62
57
67
6000
62
57
67
6750
62
57
67
7500
62
57
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
18
75°F
2
Sensible Capacity (MBH)
Total
Total
1
Cap.
Input
Return Dry Bulb (°F)
(MBH)
(kW)
90
85
88
10.6
23
21
79
10.1
44
42
70
9.9
48
46
90
10.7
32
29
81
10.2
59
56
72
10.0
61
59
92
10.8
40
36
82
10.3
73
70
73
10.0
73
73
95
10.8
49
44
85
10.2
75
74
75
10.0
75
75
98
10.7
58
52
88
10.2
78
78
78
10.0
78
78
95°F
71
11.8
12
11
64
11.4
27
25
61
11.3
30
29
74
11.8
21
19
68
11.5
46
44
64
11.4
48
48
78
11.9
29
26
71
11.5
65
62
67
11.4
67
67
79
11.9
36
32
72
11.5
67
66
68
11.4
68
68
81
11.9
43
39
73
11.5
70
70
70
11.4
70
70
115°F
60
13.3
5
4
55
12.8
15
14
53
12.8
16
15
63
13.3
12
11
58
12.9
37
36
56
12.8
37
37
66
13.4
19
17
60
12.9
59
57
59
12.9
59
59
66
13.4
25
23
61
12.9
59
58
59
12.9
59
59
66
13.4
32
28
61
12.9
59
59
59
12.9
59
59
Temperature of Air on Condenser Coil
*
Total
1
Cap.
(MBH)
80
75
70
65
19
16
14
11
80
39
37
35
32
72
44
41
39
36
66
25
22
19
15
82
53
49
46
43
74
58
55
51
48
68
32
28
23
19
85
66
61
57
53
76
72
68
64
60
70
39
33
28
23
87
72
66
61
56
78
75
70
65
59
72
46
39
33
27
90
78
71
65
59
81
78
72
65
59
74
10
8
7
6
65
24
23
22
20
60
27
26
25
24
57
16
14
12
10
69
41
39
37
35
63
47
45
43
40
60
23
20
17
14
72
59
56
52
49
66
67
63
60
57
63
29
25
21
17
73
64
60
57
53
66
68
64
60
57
64
34
30
25
21
74
70
65
61
56
67
70
65
61
56
64
4
3
3
2
54
14
13
13
12
50
15
14
14
13
50
9
8
7
6
57
35
33
32
31
53
36
35
34
33
52
15
13
11
9
60
55
53
51
49
55
58
56
54
52
54
20
18
15
12
59
57
54
52
49
55
59
56
53
51
54
25
22
19
16
59
59
56
53
49
55
59
56
53
50
54
262292-YTG-B-0107
85°F
2
Sensible Capacity (MBH)
Total
Input
Return Dry Bulb (°F)
(kW)
90
85
80
75
11.2
18
16
14
12
10.8
35
34
32
30
10.6
39
37
35
34
11.3
26
24
21
18
10.8
53
50
47
44
10.7
55
54
53
50
11.3
35
31
27
24
10.9
70
66
62
58
10.7
70
70
70
66
11.3
43
38
34
29
10.9
72
70
68
63
10.7
72
72
72
67
11.3
51
45
40
34
10.9
74
74
74
68
10.7
74
74
74
68
105°F
12.5
8
8
7
6
12.1
21
20
19
18
12.1
23
22
21
20
12.6
16
15
13
11
12.2
41
40
38
36
12.1
43
42
42
40
12.6
24
22
19
16
12.2
62
60
57
54
12.1
63
63
62
60
12.6
31
28
24
21
12.2
63
62
61
57
12.1
64
64
63
60
12.6
37
34
30
26
12.2
64
64
64
60
12.1
64
64
64
61
125°F
14.0
-
-
-
-
13.5
9
9
9
8
13.5
9
8
8
8
14.1
8
7
6
5
13.6
33
31
31
30
13.6
31
31
31
30
14.1
14
13
11
9
13.6
55
54
53
52
13.6
54
54
54
53
14.1
20
18
16
14
13.6
54
54
53
52
13.6
54
54
54
52
14.1
26
23
21
18
13.6
54
54
54
51
13.6
54
54
54
52
Unitary Products Group
*
70
65
10
9
28
26
32
30
15
12
41
39
47
44
20
16
55
51
62
58
25
20
59
55
63
58
29
24
63
58
63
58
5
4
17
16
19
18
9
8
34
33
38
36
14
11
52
49
57
55
18
15
54
51
57
54
22
18
57
53
57
53
-
-
8
8
8
8
4
3
29
29
30
29
8
6
50
49
51
50
12
10
49
47
50
48
16
13
48
46
49
46