Cooling Capacities For Wr240 (Alternate Reheat Mode) - York SUNLINE MAGNADRY WR 180 Technical Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MAGNADRY WR 180:
Table of Contents

Advertisement

262292-YTG-C-0707
TABLE 8: COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE)
Air on Evaporator Coil
WB
CFM
(°F)
67
6000
62
57
67
7000
62
57
67
8000
62
57
67
8450
62
57
67
8900
62
57
67
6000
62
57
67
7000
62
57
67
8000
62
57
67
8450
62
57
67
8900
62
57
67
6000
62
57
67
7000
62
57
67
8000
62
57
67
8450
62
57
67
8900
62
57
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Unitary Products Group
75°F
2
Sensible Capacity (MBH)
Total
Total
1
Return Dry Bulb (°F)
Cap.
Input
(MBH)
(kW)
90
85
100
15.9
20
18
93
15.1
44
42
83
15.1
50
48
109
15.8
31
28
102
15.1
68
65
90
15.0
74
74
119
15.7
42
37
110
15.0
92
88
98
14.9
98
98
113
15.7
42
38
105
15.0
88
88
93
14.9
93
93
107
15.7
42
38
99
14.9
88
88
88
14.9
88
88
95°F
87
17.3
7
6
79
16.7
16
15
72
16.5
18
18
96
17.2
20
18
88
16.6
46
44
79
16.4
53
52
106
17.2
34
30
96
16.6
76
73
87
16.4
87
86
101
17.2
36
32
92
16.6
78
78
83
16.4
83
83
96
17.2
38
35
87
16.6
79
79
79
16.4
79
79
115°F
67
19.1
-
-
57
18.7
-
-
54
18.3
-
-
75
19.1
11
10
64
18.7
27
26
61
18.3
34
33
83
19.2
21
19
71
18.7
54
52
68
18.3
68
67
80
19.1
22
19
68
18.6
55
53
65
18.2
65
65
77
19.0
22
20
65
18.5
55
53
63
18.2
63
63
Temperature of Air on Condenser Coil
*
Total
1
Cap.
(MBH)
80
75
70
65
16
14
12
10
94
40
38
36
35
86
46
45
43
41
77
24
21
18
15
103
62
59
56
53
95
71
68
64
61
85
33
29
24
20
112
83
79
75
70
103
95
91
86
82
93
33
29
25
21
107
85
80
76
72
98
92
87
83
79
88
34
30
26
22
101
86
82
78
73
93
88
84
80
76
84
5
5
4
3
77
14
14
13
12
68
17
16
16
15
63
16
14
12
10
86
42
40
38
35
76
50
48
46
44
70
27
23
20
16
94
69
66
62
59
84
83
79
76
72
78
29
25
22
18
90
75
71
68
64
80
81
77
74
70
74
31
27
24
20
86
79
75
72
67
76
79
75
72
68
71
-
-
-
-
57
-
-
-
-
46
-
-
-
-
46
8
7
6
5
64
25
24
23
21
52
32
31
30
29
52
17
15
13
10
72
50
47
45
43
58
65
62
60
58
58
17
15
13
11
70
51
48
46
44
56
64
61
59
57
56
18
16
14
12
67
51
49
47
45
54
63
61
59
56
54
85°F
2
Sensible Capacity (MBH)
Total
Return Dry Bulb (°F)
Input
(kW)
90
85
80
75
16.6
13
12
11
9
15.9
30
29
27
26
15.8
34
33
32
30
16.5
25
23
20
18
15.8
57
54
52
49
15.7
63
63
60
58
16.4
38
34
30
26
15.8
84
80
76
72
15.7
93
93
89
85
16.4
39
35
31
27
15.8
84
84
80
76
15.7
88
88
86
82
16.4
40
36
32
29
15.8
84
84
83
79
15.7
84
84
84
80
105°F
18.2
3
3
3
2
17.7
8
7
7
7
17.4
9
9
9
8
18.2
15
14
12
11
17.7
36
35
33
32
17.4
43
43
41
40
18.2
28
25
22
19
17.7
65
62
59
57
17.4
78
77
74
71
18.1
29
26
23
20
17.6
68
66
63
60
17.3
74
74
72
69
18.1
30
27
24
21
17.6
71
69
66
63
17.3
71
71
71
68
125°F
20.0
-
-
-
-
19.7
-
-
-
-
19.2
-
-
-
-
20.1
6
5
5
4
19.7
18
17
16
16
19.2
25
24
24
23
20.1
15
14
12
11
19.8
43
41
40
38
19.3
58
57
56
54
20.0
14
13
12
10
19.7
41
40
38
37
19.2
56
56
55
54
19.9
13
12
11
10
19.5
40
38
37
36
19.0
54
54
54
53
*
70
65
8
7
25
23
29
28
15
12
47
44
55
52
22
18
69
65
81
77
23
19
72
68
78
75
25
21
75
71
76
72
2
2
6
6
8
7
9
7
30
28
38
36
16
13
54
51
68
65
17
14
57
54
67
64
19
16
60
57
65
62
-
-
-
-
-
-
3
3
15
14
22
22
9
7
37
35
52
51
9
7
36
34
52
51
9
7
35
33
52
51
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline magnadry wr 240Sunline magnadry wr 300

Table of Contents