Additional R-22 Charge / Orifice Size For Various Matched Systems - York STELLAR PLUS H4DH018 THRU 060 Technical Manual

Split-system air conditioners 12 seer
Table of Contents

Advertisement

Additional R-22 Charge / Orifice Size for Various Matched Systems

ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
Outdoor Unit
1
Unit Orifice (s)
Factory R-22 Charge, lbs-oz
Indoor Coil
Coil Orifice
G2FD024(S,H)14,17
61
G2FD030(S,H)17
65
G2FD035(S,H)14
65
G2FD036(S,H)17,21
75
G2FD042(S,H)21
78
G2FD046(S,H)17
78
G2FD048(S,H)21,24
84
G2FD060(S,H)24
90
G2FD061(H)24
90
G1HD024
59
G1HD036
69
G1HD048
84
G1HD060
96
G1UA024S14,17
59
GIFA024S14,17
59
G1UA030S14
65
GIFA030S14
65
G1UA036S14,17,21
73
GIFA036S14,17,21
73
G1UA048S17
84
GIFA048S17
84
G1UA048S21
84
GIFA048S21
84
G1UA060S21,24
90
GIFA060S21,24
90
G1NA030S17H
57
G1NA030S17K
63
G1NA036S17J
67
G1NA048S21D
78
F2RC/F2FC024
61
F2RC/F2FC030
65
F2RC/F2FC036
73
F2RP/F2FP018
59
F2RP/F2FP024
61
F2RP/F2FP030
65
F2RP/F2FP036
75
F2FP040
63
F2RP/F2FP042
78
F2FP045
78
F2RP/F2FP048
84
F2RP/F2FP060
90
F2FV060
90
Footnotes:
1. These orifices are packed in the customer packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3.
A TXV Kit must be used with these units to obtain system performance (701,702,703 indicates 1TV07
Procedures:
1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.
2.Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line
set.
5.If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.
6.Due to serial compressor, hard start components are not required when using coils with TXV or solenoid valve kits.
Unitary Products Group
H4DH018S06 H4DH024S06 H4DH030S06
55, 57
61, 63
4 - 14
5 - 1
2
57 + 6
63 + 2
57 + 8
63 + 4
57 + 8
63 + 4
63 + 8
55 + 7
63 + 3
63 + 10
57 + 4
61 + 0
57 + 4
61 + 0
57 + 6
63 + 2
57 + 6
63 + 2
55 + 8
63 + 2
55 + 8
63 + 2
57 + 6
65 + 6
55 + 4
63 + 0
63 + 4
55 + 0
55 + 6
61 + 0
63 + 4
69 + 0/701
3
701
+ 14
H4DH036S06
H4DH042S06
69, 71
75, 78
5 - 4
5 - 15
System Orifice = Additional Charge, Oz
69 + 0
3
701
+ 0
69 + 3
75 + 0
69 + 3
75 + 10
75 + 13
71 + 6
75 + 13
3
71 + 7
75 + 24/702
+ 24
69 + 3
75 + 18
78 + 22
3
701
+ 0
3
701
+ 0
69 + 3
75 + 0
69 + 3
75 + 0
71 + 6
78 + 20
71 + 6
78 + 20
3
71 + 6
78 + 20/702
+ 20
3
71 + 6
78 + 20/702
+ 20
69 + 0
75 + 6
3
702
+ 15
69 + 0
73 + 3
78 + 12
3
+ 0
71 + 3
78 + 12
71 + 6
78 + 14
3
702
+ 28
78 + 23
---
036-21020-003 Rev. C (0203)
H4DH048S06
H4DH060S06
75, 78
87, 90
6 - 12
8 - 10
75 + 5
75 + 5
87+ 0
75 + 20
87 + 8
3
78 + 15
90 + 10/703
+ 10 99 + 13/703
90 + 21
75 + 14
87 + 1
90 + 5
75 + 15
87 + 7
75 + 15
87 + 7
75 + 19
87 + 7
75 + 19
87 + 7
3
78 + 16
90 + 10/703
+ 15
3
78 + 16
90 + 10/703
+ 15
75 + 12
87 + 3
75 + 8
78 + 20
75 + 16
87 + 7
90 + 10
99 + 13/703
90 + 10
Series).
99
7 - 13
3
+ 13
3
703
+ 5
99 + 9
99 + 9
99 + 9
3
+ 13
3
703
+ 0
3