Dex024 Superheat Charging; Dex030 Superheat Charging; Dex036 Superheat Charging; Dex042 Superheat Charging - York R-410A Installation Manual

R-410a affinity series 2-5 ton
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Table 13: DEX024 Superheat Charging
Outdoor
Temp
(°F)
55
65
23.4
70
20.8
75
18.3
80
15.8
85
13.2
90
12.9
95
12.5
100
10.4
105
8.3
110
6.3
115
-
Table 14: DEX030 Superheat Charging
Outdoor
Temp
(°F)
55
65
13.4
70
13.3
75
13.2
80
13.0
85
12.9
90
12.6
95
12.4
100
12.3
105
12.2
110
12.1
115
11.9
Table 15: DEX036 Superheat Charging
Outdoor
Temp
(°F)
55
65
18.2
70
18.7
75
19.1
80
19.6
85
20.0
90
20.2
95
20.5
100
20.7
105
20.9
110
21.2
115
21.4
Table 16: DEX042 Superheat Charging
Outdoor
Temp
(°F)
55
65
11.7
70
11.1
75
10.4
80
9.8
85
9.2
90
9.0
95
8.8
100
9.4
105
9.9
110
10.5
115
11.1
16
Superheat at Compressor Suction (°F), Airflow = 800 CFM
57
59
61
24.2
25.0
25.8
21.6
22.4
23.2
19.1
19.8
20.6
16.5
17.2
17.9
13.9
14.6
15.3
13.5
14.0
14.6
13.0
13.5
14.0
11.0
11.6
12.2
9.1
9.8
10.5
7.1
7.9
8.7
5.1
6.0
6.9
Superheat at Compressor Suction (°F), Airflow = 1000 CFM
57
59
61
13.9
14.4
14.9
13.8
14.2
14.7
13.6
14.1
14.5
13.5
13.9
14.3
13.3
13.7
14.1
13.0
13.4
13.7
12.7
13.0
13.3
12.6
12.9
13.2
12.5
12.7
13.0
12.3
12.6
12.9
12.2
12.5
12.7
Superheat at Compressor Suction (°F), Airflow = 1200 CFM
57
59
61
18.5
18.8
19.1
18.9
19.1
19.3
19.3
19.4
19.6
19.6
19.7
19.8
20.0
20.0
20.0
20.3
20.3
20.3
20.5
20.5
20.5
20.7
20.7
20.8
21.0
21.0
21.0
21.2
21.2
21.2
21.4
21.4
21.4
Superheat at Compressor Suction (°F), Airflow = 1400 CFM
57
59
61
12.7
13.7
14.7
11.9
12.7
13.5
11.1
11.7
12.3
10.2
10.7
11.1
9.4
9.6
9.9
9.2
9.4
9.6
9.0
9.2
9.4
9.6
9.7
9.9
10.1
10.3
10.4
10.7
10.8
10.9
11.2
11.3
11.4
Indoor Wet Bulb Temp (°F)
63
65
67
26.7
27.5
28.3
24.0
24.8
25.6
21.3
22.1
22.8
18.6
19.3
20.1
15.9
16.6
17.3
15.2
15.8
16.4
14.5
15.0
15.5
12.8
13.4
14.1
11.2
11.9
12.6
9.5
10.3
11.2
7.9
8.8
9.7
Indoor Wet Bulb Temp (°F)
63
65
67
15.4
15.9
16.4
15.2
15.7
16.1
15.0
15.4
15.9
14.7
15.2
15.6
14.5
14.9
15.3
14.1
14.4
14.8
13.7
14.0
14.3
13.5
13.8
14.1
13.3
13.6
13.9
13.2
13.4
13.7
13.0
13.2
13.5
Indoor Wet Bulb Temp (°F)
63
65
67
19.4
19.7
20.0
19.6
19.8
20.0
19.7
19.9
20.0
19.9
19.9
20.0
20.0
20.0
20.0
20.3
20.3
20.3
20.6
20.6
20.6
20.8
20.8
20.8
21.0
21.0
21.0
21.2
21.2
21.2
21.4
21.4
21.4
Indoor Wet Bulb Temp (°F)
63
65
67
15.7
16.7
17.7
14.3
15.1
15.9
12.9
13.5
14.2
11.5
11.9
12.4
10.1
10.4
10.6
9.9
10.1
10.3
9.6
9.8
10.0
10.1
10.3
10.5
10.6
10.7
10.9
11.1
11.2
11.4
11.6
11.7
11.8
288429-YIM-A-0307
69
71
73
28.1
27.9
27.8
25.7
25.9
25.9
23.3
23.8
24.1
20.9
21.8
22.2
18.5
19.7
20.3
17.7
19.0
19.7
16.9
18.3
19.0
15.8
17.5
18.3
14.6
16.6
17.6
13.5
15.8
16.9
12.3
14.9
16.2
69
71
73
17.4
18.3
18.8
17.1
18.0
18.5
16.8
17.7
18.1
16.4
17.3
17.8
16.1
17.0
17.4
15.7
16.7
17.2
15.3
16.4
16.9
15.1
16.2
16.7
14.9
16.0
16.5
14.7
15.8
16.3
14.5
15.6
16.1
69
71
73
20.6
21.3
21.6
20.6
21.1
21.4
20.5
21.0
21.2
20.4
20.8
21.0
20.3
20.6
20.8
20.7
21.0
21.2
21.0
21.4
21.6
21.3
21.7
21.9
21.5
22.0
22.3
21.8
22.3
22.6
22.0
22.6
22.9
69
71
73
20.0
22.3
23.4
17.9
19.8
20.8
15.8
17.4
18.2
13.7
15.0
15.6
11.6
12.5
13.0
11.2
12.1
12.6
10.9
11.8
12.2
11.4
12.4
12.9
12.0
13.1
13.6
12.5
13.7
14.3
13.1
14.4
15.0
Unitary Products Group
75
27.7
26.0
24.3
22.6
20.9
20.3
19.7
19.2
18.6
18.1
17.5
75
19.3
18.9
18.6
18.2
17.8
17.6
17.4
17.2
17.0
16.8
16.6
75
21.9
21.7
21.4
21.2
21.0
21.4
21.8
22.2
22.5
22.9
23.2
75
24.5
21.8
19.0
16.2
13.5
13.1
12.6
13.4
14.1
14.9
15.6