Cooling Airflow Data - Mv Models; High / Low Speed Cooling And Heat Pump Cfm; Heating Airflow Data - Mv Models - York MV Technical Manual
Modular variable speed air handlers for use with split system cooling & heat pump 1200 - 2000 cfm blowers 3 - 5 ton coils optional 1 & 3φ electric heaters
All CFM's are shown at 0.5" w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0" to
0.6" w.c. static pressure. From 0.6" to 1.0" static pressure, CFM is reduced by 2% per 0.1" increase in static. Operation on duct systems with greater than 1.0" w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ "D" tap should not be used.
HEATING AIRFLOW DATA - MV MODELS
12B Air Handler
CFM
High
Low
1270
791
943
714
931
643
693
567
16C Air Handler
CFM
High
Low
1884
1217
1558
1065
1336
823
1214
727
All CFM's are shown at 0.5" w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0" to
0.6" w.c. static pressure. From 0.6" to 1.0" static pressure, CFM is reduced by 2% per 0.1" increase in static. Operation on duct systems with greater than 1.0" w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.