Cooling Capacity - Coil Only - York MV Technical Manual

Modular variable speed air handlers for use with split system cooling & heat pump 1200 - 2000 cfm blowers 3 - 5 ton coils optional 1 & 3φ electric heaters
Table of Contents

Advertisement

255427-YTG-F-1006

COOLING CAPACITY - COIL ONLY

Blower
Model
Model
MC30B**H
MV12B
MC36B**H
MC48D**H
MV12D
MC60D**H
MC61D**H
MC42C**H
MV16C
MC48C**H
MC48D**H
MV20D
MC60D**H
MC61D**H
Unitary Products Group
Coil
Rated
CFM
Multi-Position - Upflow / Downflow / Horizontal
1025
1250
1125
1275
1450
1400
1650
1725
2000
2200
Entering Air °F
(Dry / Wet Bulb)
35 / 61.5
85 / 72
41.5
80 / 67
36.2
75 / 62
29.1
70 / 57
24.1
85 / 72
52.0
80 / 67
41.7
75 / 62
32.5
70 / 57
27.9
85 / 72
46.8
80 / 67
37.4
75 / 62
28.9
70 / 57
25.1
85 / 72
53.7
80 / 67
43.0
75 / 62
33.1
70 / 57
28.8
85 / 72
91.7
80 / 67
73.4
75 / 62
57.3
70 / 57
49.2
85 / 72
88.4
80 / 67
70.8
75 / 62
55.2
70 / 57
47.4
85 / 72
100.5
80 / 67
80.4
75 / 62
62.7
70 / 57
53.9
85 / 72
119.9
80 / 67
96.0
75 / 62
74.0
70 / 57
64.3
85 / 72
124.8
80 / 67
99.9
75 / 62
77
70 / 57
66.9
85 / 72
131.0
80 / 67
104.9
75 / 62
81.8
70 / 57
70.2
MBH @ Evaporator Temperature and
Corresponding Pressure °F / PSIG
40 / 68.5
45 / 76.0
37.8
33.7
32.4
28.6
25.3
24.0
21.5
18.7
47.3
42.3
36.8
32.3
27.3
29.8
25.8
23.8
42.4
37.6
33.3
29.4
24.6
21.7
23.3
21.7
48.4
43.5
38.0
33.3
28.1
24.5
26.5
24.5
78.4
68.1
61.5
52.0
45.6
38.4
43.0
38.4
76.0
63.3
59.4
48.4
43.9
35.8
41.5
35.8
86.4
72.0
67.5
55.0
49.9
40.7
47.2
40.7
101.0
80.0
79.2
62.6
58.6
46.2
55.4
46.2
105.2
85.3
82.5
65.2
61.1
48.1
57.7
48.1
110.5
89.6
86.6
68.5
64.2
50.5
60.6
50.5
50 / 84.0
29.5
24.5
19.2
15.8
37.3
27.4
22.2
22.2
33.0
24.3
19.6
19.6
37.5
27.7
22.4
22.4
52.3
38.6
31.2
31.2
50.0
37.0
29.9
29.9
56.8
42.1
34.0
34.0
62.2
45.8
37.0
37
64.7
47.7
38.6
38.6
67.9
50.1
40.5
40.5
3