262259-YTG-B-0107
TABLE 6: DM 300 COOLING CAPACITIES (25 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
POWER
1
CAP.
INPUT
WB
MBH
CFM
°F
77
298.7
72
277.7
7500
67
256.6
62
236.9
57
234.7
77
302.4
72
281.1
8750
67
259.8
62
239.9
57
237.6
77
306.1
72
284.5
10000
67
263.0
62
242.8
57
240.5
72
287.9
67
266.1
11250
62
245.7
57
243.3
72
291.3
67
269.3
12500
62
248.6
57
246.2
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
2
KW
90
85
80
36.0
144.7 109.0
73.4
35.4
199.3 163.7 128.1
92.4
34.8
254.0 218.4 182.7 147.1 111.5
34.0
236.9 236.6 201.0 165.4 129.7
34.5
234.7 234.7 202.9 167.2 131.6
36.1
183.4 120.5
78.3
35.5
221.0 178.8 136.7
94.6
34.9
258.5 237.2 195.1 153.0 110.9
34.1
239.9 239.7 214.6 172.5 130.4
34.6
237.6 237.6 216.6 174.5 132.4
36.3
222.2 131.9
83.3
35.7
242.6 194.0 145.4
96.8
35.1
263.0 256.1 207.5 158.9 110.3
34.2
242.8 242.8 228.2 179.6 131.0
34.8
240.5 240.5 230.4 181.8 133.2
35.9
258.4 203.1 147.7
92.4
35.3
266.1 262.7 210.8 155.4 100.1
34.5
245.7 245.7 231.8 176.5 121.1
35.0
243.3 243.3 234.0 178.7 123.3
36.1
274.2 212.1 150.0
87.9
35.5
269.3 269.3 214.1 152.0
34.7
248.6 248.6 235.5 173.4 111.3
35.2
246.2 246.2 237.7 175.6 113.5
75
70
65
-
-
-
-
-
-
94.1
96.0
-
-
-
-
-
-
88.2
90.3
-
-
-
-
-
-
82.4
84.6
-
-
-
65.8
68.0
-
-
89.9
-
49.2
51.4
15