York DM 180 Technical Manual page 11

Single package gas/electric units and single package air conditioners 15, 20 & 25 nominal tons
Table of Contents

Advertisement

262259-YTG-B-0107
TABLE 4: DM 180 COOLING CAPACITIES (15 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
POWER
1
CAP.
INPUT
WB
MBH
CFM
°F
77
176.8
72
161.9
4500
67
147.0
62
135.8
57
135.8
77
183.4
72
167.9
5250
67
152.5
62
140.9
57
140.9
77
190.0
72
174.0
6000
67
158.0
62
146.0
57
146.0
72
178.4
67
162.0
6750
62
149.7
57
149.7
72
182.8
67
166.0
7500
62
153.4
57
153.4
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 1.5 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Unitary Products Group
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
2
KW
90
85
80
20.4
98.3
77.0
55.6
19.5
124.1 102.7
81.3
59.9
18.6
147.0 128.4 107.0
85.6
18.1
135.8 135.8 121.1
99.7
18.2
135.8 135.8 121.1
99.7
20.5
126.5
86.6
61.3
19.6
140.2 114.9
89.6
64.4
18.8
152.5 143.2 118.0
92.7
18.3
140.9 140.9 133.6 108.3
18.4
140.9 140.9 133.6 108.3
20.7
154.6
96.3
67.0
19.8
156.3 127.2
98.0
68.8
18.9
158.0 158.0 129.0
99.8
18.4
146.0 146.0 146.0 116.8
18.5
146.0 146.0 146.0 116.8
20.1
169.6 140.7 107.5
74.3
19.2
162.0 162.0 141.5 108.3
18.6
149.7 149.7 149.7 116.5
18.7
149.7 149.7 149.7 116.5
20.3
182.8 154.3 117.0
79.7
19.4
166.0 166.0 154.0 116.7
18.9
153.4 153.4 153.4 116.1
19.0
153.4 153.4 153.4 116.1
75
70
65
-
-
-
-
-
64.2
-
78.3
56.9
78.3
56.9
-
-
-
-
-
67.5
-
83.0
57.7
83.0
57.7
-
-
-
-
-
70.7
-
87.7
58.5
87.7
58.5
-
-
75.1
-
83.3
50.1
83.3
50.1
-
-
79.5
-
78.9
41.6
78.9
41.6