screen the following values are displayed from top to bottom; Suction Pressure,
Suction Temperature and Evaporation Temperature. In the lower left corner of
the screen the following is displayed from top to bottom; Valve Steps, Valve % Open,
Valve Status and Valve Emergency Controls Status.
The Valve Status can be one of the three values:
The Valve Controls Status can be one of the four values:
To return to the MAIN MENU, press the Esc key.
2.3.3 Occupancy Schedule (Figure 8)
Select the OCCUPANCY SCHEDULE from the MAIN MENU to enable a schedule to
place the dehumidifier in the occupied mode. See Figure 7. To enable a schedule
select Yes, and press ENTER. The schedule will need to be setup before this will be
enabled. Pressing the Prg key from this menu allows the date and time to be modified.
To return to the MAIN MENU, press the Esc key.
"---" – Value is not initialized (Unit Size not set)
"On" – Value is operating
"Off" – Value is Standby
"Low SH" – Low Superheat Controls
"LOP" – Low Operating Pressure Controls
"MOP" – High Operating Pressure Controls
"Hi TCond" – High Condensing Temperature Controls
Figure 7
Desert Aire - CM3540 Manual
17