Page 3
We gratefully accept suggestions for improvement. Trademarks VIPA, System 100V, System 200V, System 300V and System 500V are registered trademarks of VIPA Gesellschaft für Visualisierung und Prozessautomatisierung mbH. SIMATIC, STEP, ET200 and S7-300 are registered trademarks of Siemens AG.
Page 4
Digital in-/output modules These chapters introduce you to the digital peripheral modules of the System 300V from VIPA and contain all information that you will need for installation. Chapter 3 contains information about the digital input modules, chapter 4 describes the digital output modules and chapter 5 concerns to the combined input/output modules.
User considerations ................. 1 Safety information ..................2 Chapter 1 Basics ..................1-1 Safety Information for Users ................1-2 General description of the System 300V............1-3 Components....................... 1-4 Chapter 2 Assembly and installation guidelines ........2-1 Overview ......................2-2 Installation dimensions..................2-3 Installation at the profile rail ................
Page 6
Manual VIPA System 300V Contents HB130E - SM - Rev. 07/44...
Manual VIPA System 300V User considerations User considerations This manual describes the signal modules (SM) that can be used with the Objective and System 300. It contains a description of construction, project implemen- contents tation and application of the products as well as the technical data.
Manual VIPA System 300V Safety information Safety information The modules of the System 300V are constructed and manufactured for Application specifications • System 300 components from VIPA and Siemens • communication and process control • general control and automation tasks •...
Main theme of this chapter is to give you an overview about the System Outline 300V from VIPA. We will outline the possibilities of the installation of central res. decentral systems. This chapter also contains general information about the System 300V like measurements, hints for installation and the environmental conditions.
Manual VIPA System 300V Chapter 1 Basics Safety Information for Users VIPA modules make use of highly integrated components in MOS- Handling of Technology. These components are extremely sensitive to over-voltages electrostatically that can occur during electrostatic discharges. sensitive modules The following symbol is attached to modules that can be destroyed by electrostatic discharges.
Manual VIPA System 300V Chapter 1 Basics General description of the System 300V The System 300V is a modular automation system for middle and high The System 300V performance needs, that you can use either distributed or non-distributed. The single modules are directly clipped to a 530 mm backplane and are connected together with the help of bus clips at the backside.
CPU via MPI. Another component of the decentral system is the CAN-Slave. It allows the link-up to the fieldbus system CANopen. A large number of peripheral modules are available from VIPA, for example Peripheral digital as well as analog inputs/outputs.
Page 13
Please note that the maximum current that the integrated power supply can deliver to the backplane bus is 3.5A. The power supply is protected against reverse polarity and overcurrent. The digital in-/output modules of the System 300V from VIPA are pin and Compatibility function compatible to Siemens.
Page 14
Manual VIPA System 300V Chapter 1 Basics HB130E - SM - Rev. 07/44...
Assembly and installation guidelines In this chapter you will find all information, required for the installation and Outline the cabling of a process control with the components of the System 300V. The following text describes: • General overview • Steps of installation and cabling •...
2000mm 15mm * Unit pack: 10 pieces For the communication between the modules the System 300V uses a Bus connector backplane bus connector. The backplane bus connector are included in the delivering of the peripheral modules and are clipped at the module from behind before installing it to the profile rail.
Manual VIPA System 300V Chapter 2 Assembly and installation guidelines Installation dimensions Here follows all the important dimensions of the System 300V. Overview 1tier width (WxHxD) in mm: 40 x 125 x 120 Dimensions Basic enclosure 2tier width (WxHxD) in mm: 80 x 125 x 120...
Manual VIPA System 300V Chapter 2 Assembly and installation guidelines Installation at the profile rail You may install the System 300V as well horizontal as vertical. Please Structure: regard the allowed environment temperatures: • horizontal structure: from 0 to 60°...
Page 19
Danger! • Before installing or overhauling the System 300V, the power supplies must be disconnected from voltage (pull the plug or remove the fuse)! • Installation and modifications only by properly trained personnel!
The power supplies and CPUs are exclusively delivered with CageClamp Outline contacts. For the signal modules the front connectors are available from VIPA with screw contacts. In the following all connecting types of the power supplies, CPUs and input/output modules are described. Danger! •...
Page 21
Manual VIPA System 300V Chapter 2 Assembly and installation guidelines For the cabling of e.g. the power supply of a CPU, green plugs with CageClamp CageClamp technology are deployed. technology (green) Here also you may connect wires with a cross-section of 0.08 mm 2.5 mm...
Page 22
In the following the cabling of the three variants of the front-facing Front connectors connector is shown: of the in-/output For the I/O modules the following plugs are available at VIPA: modules 20pole screw connection 40pole screw connection VIPA 392-1AJ00 VIPA 392-1AM00 Open the front flap of your I/O module.
Page 23
Manual VIPA System 300V Chapter 2 Assembly and installation guidelines ... continue 20pole screw connection 40pole screw connection Push the release key at the front connector on Bolt the fixing screw of the front connector. the upper side of the module and at the same time push the front connector into the module until it locks.
The installation guidelines contain information about the interference free General deployment of System 300V systems. There is the description of the ways, interference may occur in your control, how you can make sure the electromagnetic digestibility (EMC), and how you manage the isolation.
Page 25
- Please take care for the targeted employment of the grounding actions. The grounding of the PLC is a protection and functionality activity. - Connect installation parts and cabinets with the System 300V in star topology with the isolation/protected earth conductor system. So you avoid ground loops.
Page 26
• Lay the isolation on an isolation rail directly after the entry of the cable in the cabinet. Lead the isolation further on to the System 300V module and don't lay it on there again!
Manual VIPA System 300V Chapter 3 Digital Input Modules Chapter 3 Digital Input Modules This chapter contains a description of the structure and the operation of the Outline VIPA digital input modules. The following text describes: • System overview of digital input modules •...
Manual VIPA System 300V Chapter 3 Digital Input Modules System overview In the following you find an overview over the digital input modules that are Input Modules available at VIPA: SM 321 DI 16xAC120/230V DI 16xDC24V DI 32xDC24V SM321 SM321...
Manual VIPA System 300V Chapter 3 Digital Input Modules 321-1BH01 - DI 16xDC 24V DI 16xDC 24V VIPA 321-1BH01 Order data The digital input module collects the binary control signals from the process Description level and transmits them isolated to the superordinated bus system. It has 16 channels and their status is monitored via LEDs.
Page 30
Manual VIPA System 300V Chapter 3 Digital Input Modules Input module Schematic diagram Optocoupler DC 24V intern Technical Data Module name VIPA 321-1BH01 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of inputs Programming specifications...
Manual VIPA System 300V Chapter 3 Digital Input Modules 321-1BL00 - DI 32xDC 24V DI 32xDC 24V VIPA 321-1BL00 Order data The digital input module collects the binary control signals from the process Description level and transmits them isolated to the superordinated bus system. It has 32 channels and their status is monitored via LEDs.
Page 32
Manual VIPA System 300V Chapter 3 Digital Input Modules Schematic Schematic diagram Numeric representation diagram Numeric Input module Input module: Process image: +0 +2 representation Address 00000011b Optocoupler DC 24V 00001100b 00110000b 11000000b SM321 +1 +3 intern Technical Data Module name...
Manual VIPA System 300V Chapter 3 Digital Input Modules 321-1FH00 - DI 16xAC120/230V DI 16xAC 120/230V VIPA 321-1FH00 Order data The digital input module collects the binary control signals from the process Description level and transmits them isolated to the superordinated bus system.
Page 34
Manual VIPA System 300V Chapter 3 Digital Input Modules Input module Schematic diagram AC 120/230V Optocoupler V-Bus intern Technical Data Module name VIPA 321-1FH00 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of inputs Length of cable - unshielded max.
Manual VIPA System 300V Chapter 4 Digital Output Modules Chapter 4 Digital Output Modules This chapter contains a description of the structure and the operation of the Outline VIPA digital output modules. The following text describes: • System overview of digital output modules •...
Manual VIPA System 300V Chapter 4 Digital Output Modules System overview In the following you will get an overview over the digital output modules that Output modules are available at VIPA: SM 322 DC 24V output modules DO 16xDC24V DO 8xDC24V...
Page 37
Manual VIPA System 300V Chapter 4 Digital Output Modules AC 120/230V Output module DO8xAC120/230V SM322 VIPA 322-5FF00 Order data Type Order No. Page AC 120/230V DO 8xAC 120/230V 2A VIPA 322-5FF00 4-16 output modul Relay output module DO 16xRELAIS SM322...
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-1BF01 - DO 8xDC 24V 2A DO 8xDC 24V 2A VIPA 322-1BF01 Order data The digital output module collects the binary control signals from the Description superordinated bus system and transmits them isolated to the process level.
Page 39
Manual VIPA System 300V Chapter 4 Digital Output Modules Output module Schematic diagram Optocoupler DC 24V intern Technical data Module name VIPA 322-1BF01 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 180g Data for specific module Number of outputs Length of cable...
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-1BH01 - DO 16xDC 24V 1A DO 16xDC 24V 1A VIPA 322-1BH01 Order data The digital output module collects the binary control signals from the Description superordinated bus system and transmits them isolated to the process level.
Page 41
Manual VIPA System 300V Chapter 4 Digital Output Modules Output module Schematic diagram Optocoupler DC 24V intern Technical Data Module name VIPA 322-1BH01 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of outputs Programming specifications...
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-1BH41 - DO 16xDC 24V 2A DO 16xDC 24V 2A VIPA 322-1BH41 Order data The digital output module collects the binary control signals from the Description superordinated bus system and transmits them isolated to the process level.
Page 43
Manual VIPA System 300V Chapter 4 Digital Output Modules Output module Schematic diagram Optocoupler DC 24V intern Technical Data Module name VIPA 322-1BH41 Dimensions and weight Dimensions WxHxD mm 40x125x120mm Weight 200g Data for specific module Number of outputs Programming specifications...
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-1BH60 - DO 16xDC 24V 0.5A for manual operation DO 16xDC 24V 0.5A HB VIPA 322-1BH60 Order data The module is configured as in-/output module. It has 16 channels and Description their status is monitored via LEDs.
Page 45
Manual VIPA System 300V Chapter 4 Digital Output Modules Front switch Schematic Automatic (A) Output module diagram Hand (0) / (1) H (0) Optocoupler H (1) internal DC 24V Please regard that the module is installed as 323-1BL00. You are allowed Deployment to request the switch position of the according channel via the input word.
Page 46
Manual VIPA System 300V Chapter 4 Digital Output Modules Technical Data Module name VIPA 322-1BH60 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of outputs Number of inputs 1 (switch input for A.x="1") Length of cable...
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-1BL00 - DO 32xDC 24V 1A DO 32xDC 24V 1A VIPA 322-1BL00 Order data The digital output module collects the binary control signals from the Description superordinated bus system and transmits them isolated to the process level.
Page 48
Manual VIPA System 300V Chapter 4 Digital Output Modules Pin assignment Status monitor Assignment Description Supply voltage 1L+ 1/3L+, 2/4L+ LED (green) DO 32xDC24V 1/3L+ Output Q+0.0 supply voltage is on Output Q+0.7 .0 ..7 LEDs (green) Ground 1 Q+0.0 to Q+3.7...
Page 49
Manual VIPA System 300V Chapter 4 Digital Output Modules From the application level to the hardware level the data is stored in Numeric Motorola-Format, i.e. "ready for reading". representation The following picture shows the output of the number 287454020dez res.
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-5FF00 - DO 8xAC 120/230V 2A DO 8xAC 120/230V 2A VIPA 322-5FF00 Order data The digital output module collects the binary control signals from the Description superordinated bus system and transmits them isolated to the process level.
Page 51
Manual VIPA System 300V Chapter 4 Digital Output Modules Pin assignment Status monitor Assignment Description Rated load voltage 1L LED (red) DO8xAC120/230V Q+0.0 Group errror LED, Rated load voltage 2L error if module is not supplied with parameters Q+0.1 by the CPU Rated load voltage 3L Q+0.2...
Page 52
Simatic 300 > CPU 300 > CPU 315-2 DP. • Link-up your System 300V modules in the plugged-in sequence starting with slot 4. Here the digital output modules of VIPA are to be projected as digital output modules of Siemens in accordance with the following...
Page 53
Manual VIPA System 300V Chapter 4 Digital Output Modules If the module gets parameters, which are not supported by the module, for Parameterization example a current module is to be configured as a voltage module, these during run time by parameters are interpreted as wrong parameters and an error is initialized.
Page 54
Manual VIPA System 300V Chapter 4 Digital Output Modules Technical Data Module name VIPA 322-5FF00 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of outputs Length of cable - unshielded 600m - shielded 1000m Programming specifications...
Manual VIPA System 300V Chapter 4 Digital Output Modules 322-1HH00 - DO 16xRelay DO 16xRelais VIPA 322-1HH00 Order data The relay output module collects the binary control signals from the Description superordinated bus system and transmits them via relay outputs to the process level.
Page 56
Manual VIPA System 300V Chapter 4 Digital Output Modules Circuit diagram Circuit diagram Schematic diagram Schematic diagram Relay output module Optocoupler DC 24V backplane L+ DC 24V intern When using inductive load please Note: take an suitable protector! Maximum toggle capacity...
Page 57
Manual VIPA System 300V Chapter 4 Digital Output Modules Technical Data Module name VIPA 322-1HH00 Dimensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of outputs 16 via relay Programming specification Output data 2Byte Voltages, Currents, Potentials...
Page 58
Manual VIPA System 300V Chapter 4 Digital Output Modules 4-24 HB130E - SM - Rev. 07/44...
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules Chapter 5 Digital Input/Output Modules This chapter contains a description of the structure and the operation of the Outline VIPA digital in-/output modules. The following text describes: • System overview of digital input/output modules •...
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules System overview In the following you will get an overview over the digital input/output I/O modules modules that are available at VIPA: SM 323 DI8/DO8xDC24V DIO 16xDC24V DIO 32xDC24V SM323 SM323...
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules 323-1BH00 - DIO 16xDC 24V 1A DIO 16xDC 24V 1A VIPA 323-1BH00 Order Data The module is a combined module. It has 16 channels that can be used Description either as inputs or outputs. Every channel supports a diagnostic function, i.e.
Page 62
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules Input/Output module Schematic Optocoupler diagram intern DC 24V Optocoupler intern Technical Data Module name VIPA 323-1BH00 Dimensions and Weight Dimensions WxHxD 40x125x120mm Weight 210g Data for specific module Number of Inputs...
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules 323-1BH01 - DI 8xDC 24V, DO 8xDC 24V 1A DI 8xDC 24V, DO 8xDC 24V 1A VIPA 323-1BH01 Order Data The module has 16 channels, isolated to the back panel bus, where 8 Description working as inputs and the 8 working as outputs.
Page 64
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules Input module Output module Schematic diagram Optocoupler Optocoupler DC 24V DC 24V intern intern Technical Data Module name VIPA 323-1BH01 Dimensions and Weight Dimensions WxHxD 40x125x120mm Weight 210g Data for specific module...
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules 323-1BL00 - DI 16xDC 24V, DO 16xDC 24V 1A DI 16xDC24V, DO 16xDC24V 1A VIPA 323-1BL00 Order Data The module has 32 channels, isolated to the back plane bus, with 16 inputs Description and 16 outputs.
Page 66
Manual VIPA System 300V Chapter 5 Digital Input/Output Modules Input module Output module Schematic diagram Optocoupler Optocoupler DC 24V DC 24V intern intern Technical Data Module name VIPA 323-1BL00 Dimensions and Weight Dimensions WxHxD 40x125x120mm Weight 210g Data for specific module...
Manual VIPA System 300V Chapter 6 Analog Input Modules Chapter 6 Analog Input Modules This chapter contains a description of the structure and the operation of the Overview VIPA analog input modules. The following text describes the: • System overview over the analog input modules •...
Manual VIPA System 300V Chapter 6 Analog Input Modules System overview The following gives you an overview of the analog input modules of the Input modules System 300V available from VIPA: SM 331 AI 8x13Bit AI 8x12Bit AI 2x12Bit SM331...
Please take care of the correct polarity when installing the measuring transducer! Please install short circuits at non-used inputs by connecting the positive contact with the channel ground of the according channel. The analog input modules from VIPA do not have any measuring range Parameterization plug.
Simatic 300 > CPU 300 > CPU 315-2 DP. • Link-up your System 300V modules in the plugged-in sequence starting with slot 4. Here the analog input modules of VIPA are to be projected as analog input modules of Siemens:...
Page 71
Manual VIPA System 300V Chapter 6 Analog Input Modules By using the SFCs 55, 56 and 57 you may change the parameters of the Parameterization analog modules during runtime via the CPU. The time needed until the new during runtime parameterization is valid can last up to a few ms.
Page 72
Manual VIPA System 300V Chapter 6 Analog Input Modules As shown in the following illustration the parameter mode is made up of the Get mode coding of the measuring range and measuring type during run time parameterization each channel respectively channel group.
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-1KF01 - AI 8x13Bit AI 8x13Bit VIPA 331-1KF01 Order data The analog input module transforms analog signals from the process into Description digital signals for the internal processing. The module is pin and function compatible to the known module from Siemens.
Page 75
Manual VIPA System 300V Chapter 6 Analog Input Modules The following illustration shows the connection options for the different Wiring diagrams measuring ranges. The assignment to the measuring ranges is to find in the column "Conn." of the table "Measuring" on the next pages.
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-1KF01 - AI 8x13Bit - Parameterization After Power ON the module is set to ±10V for all channels with an Overview integration time of 60ms. Via a hardware configuration you may parameterize the channels individually.
Page 77
Manual VIPA System 300V Chapter 6 Analog Input Modules At the parameterization, a parameter area of 14Byte length is stored in the Structure of record set 1. Under deploying the SFCs 55, 56 and 57, you may alter the parameter byte parameters during run time and transfer them to your analog module.
Page 78
Manual VIPA System 300V Chapter 6 Analog Input Modules The following section shows an overview of all measuring types and ranges Mode per Channel plus binary coding for the parameterization. Additionally, the wiring diagram Bit-No. Byte 2 ...9 assigned to the measuring range is shown in brackets.
Page 79
Manual VIPA System 300V Chapter 6 Analog Input Modules Measuring type Thermo resistance measuring (Measuring type coding: 1001b), wiring diagram (Conn.: 4, 5, 6) Unit Unit Unit Range °C °F Meas. range Range dec. dec. dec. coding (0.1°C/digit) (0.1°F/digit) (0.1K/digit) End Overdrive 1000.0...
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-1KF01 - AI 8x13Bit - Technical Data Module name VIPA 331-1KF01 Dimensions and Weight Dimensions (WxHxD in mm) 40x125x120 Weight ca. 205g Data for specific module Number of inputs - for 4wire resistance-type sensor...
Page 81
Manual VIPA System 300V Chapter 6 Analog Input Modules ... continue Analog value generation VIPA 331-1KF01 - Noise suppression for frequency f1 in Hz 50Hz 60Hz - Basic execution time of the module in ms (all 488ms 408ms channels released)
Page 82
Manual VIPA System 300V Chapter 6 Analog Input Modules ... continue Data for selecting a sensor VIPA 331-1KF01 Input range Input resistance ± 50mV, ± 500mV, ± 1V - Voltage 100MΩ ±5V, 1...5V, ±10V, 0...10V 100kΩ - Current ±20mA, 0...20mA, 4...20mA 100Ω...
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-7Kx01 - AI 8(2)x12Bit AI 8x12Bit VIPA 331-7KF01 Order data AI 2x12Bit VIPA 331-7KB01 The analog input modules transform analog signals from the process into Description digital signals for the internal processing. The modules are pin and function compatible to the modules from Siemens with the same name.
Page 84
Manual VIPA System 300V Chapter 6 Analog Input Modules Pin assignment status monitor Assignment Connection 331-7KF01 Description Power supply DC 24V AI 8x12Bit LED (red) + Channel 0 Group error, ON as Ground Channel 0 soon as a diagnostic + Channel 1...
Page 85
Manual VIPA System 300V Chapter 6 Analog Input Modules Regarding the fact, that parameterized inputs can be left unused due to the Connection of building of channel groups, you have to connect the unused inputs with the sensors associated ground.
Page 86
Manual VIPA System 300V Chapter 6 Analog Input Modules The thermo pair consists of two wires of different metals or metal alloys Installation of which are soldered or welded together at the ends. The different combi- thermocouples nations of metals cause different thermocouple types, e.g. K, J, N.
Page 87
Manual VIPA System 300V Chapter 6 Analog Input Modules Thermocouples with compensation slot Copper cables When connecting thermocouples with one compensation slot, you have to regard that the thermocouples have the same type. The compensation slot is to be connected at COMP+ and COMP- and is to be supplied external.
Page 88
Manual VIPA System 300V Chapter 6 Analog Input Modules Starting with firmware version 1.3.8 of the analog module, there is the Thermocouples possibility to connect a Pt100 reference junction for compensation. with Pt100 With this connection variant the temperature of the reference junction is reference junction evaluated by means of a Pt100 resistance thermometer.
Page 89
Manual VIPA System 300V Chapter 6 Analog Input Modules The analog values are only processed by the CPU in binary representation. Analog value Hereby the process signals are transformed into digital format in the analog representation module and passed on to the CPU as word variable.
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-7Kx01 - AI 8(2)x12Bit - Parameterization After power ON every channel of the modules is adjusted to ±10V with an Overview interference frequency of 50Hz. The diagnostic function is deactivated. At the parameterization, a record set of 16Byte length is transferred to both modules.
Page 91
Manual VIPA System 300V Chapter 6 Analog Input Modules At the parameterization, a parameter area of 16Byte length is stored in the Structure of the record sets 0 and 1. Here the data irrelevant for the module AI 2x12Bit parameter bytes (331-7KB01) are ignored.
Page 92
Manual VIPA System 300V Chapter 6 Analog Input Modules The following section shows an overview of all measuring types and ranges Modus per plus binary coding for the parameterization. channel pair Measuring type Voltage measuring (Measuring type coding: 0001b) Range...
Page 93
Manual VIPA System 300V Chapter 6 Analog Input Modules Measuring type 4wire Resistance measuring (Measuring type coding: 0100b) Range Measuring range Range / Representation coding 176.383 Ohm = End Overdrive region (32511) 150 Ohm 0...150 Ohm = Nominal range ( 0...27648)
Page 94
Manual VIPA System 300V Chapter 6 Analog Input Modules Measuring type Thermocouple: compensation external, linear (Measuring type coding: 1110b) compensation internal, linear (Measuring type coding: 1110b) Range Measuring range Range / Representation in °C (0.1°C/digit) coding 1450°C = End Overdrive region...
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-7Kx01 - AI 8(2)x12Bit - Diagnostics As soon as an error occurs, like "wire break" or "measuring value out of Diagnostics range", an entry is made in the diagnostic area that can be evaluated by means of the user application.
Page 96
Manual VIPA System 300V Chapter 6 Analog Input Modules Every analog input module sends, independent from the parameterization, Error indication the measuring value 7FFFh at overflow and 8000h at underflow when via measuring recognizing an error. value and LEDs At activated group diagnosis the group diagnosis-LED (SF) and the error- LED that is assigned to that channel are blinking.
Page 97
Manual VIPA System 300V Chapter 6 Analog Input Modules Byte 0 to 15: Diagnostics record set 1 The record set 1 contains the 4Byte of record set 0 and additionally 12Byte module specific diagnostic data. The diagnostic bytes have the following assignment:...
Page 98
Manual VIPA System 300V Chapter 6 Analog Input Modules Message Possible error cause Remedial Error cause and remedy Project Parameterization at run Proof the parameteri- engineering/ time: zation during run time Parameterization Wrong function code in error record set Wire break...
Page 99
Manual VIPA System 300V Chapter 6 Analog Input Modules Process interrupts are limit value interrupts. They occur if they are released Process via parameterization and a measuring value is outside the defined range. interrupts Process interrupts may only parameterized for the channels 0 and 2.
Page 100
Manual VIPA System 300V Chapter 6 Analog Input Modules At a process interrupt the CPU interrupts the user application and branches Reaction to a the into the OB 40. process interrupt More detailed information about the channel, which limit value has been exceeded, are stored in the OB 40 in the variable OB 40_POINT_ADR in the local data double word 8 (LD 8).
Manual VIPA System 300V Chapter 6 Analog Input Modules 331-7Kx01 - AI 8(2)x12Bit - Technical Data Module name VIPA 331-7KF01 VIPA 331-7KB01 Dimensions and Weight Dimensions (WxHxD in mm) 40x125x117 Weight ca. 200g Data for specific module Number of inputs...
Page 102
Manual VIPA System 300V Chapter 6 Analog Input Modules ... continue Analog value generation VIPA 331-7KF01 VIPA 331-7KB01 Measuring principle Sigma delta Integration time/conversion time/resolution (per channel) - programmable - Conversion rate in Hz - Integration time in ms 100 2.5...
Page 103
Manual VIPA System 300V Chapter 6 Analog Input Modules ... continue ... Suppression of interference, limits error VIPA 331-7KF01 VIPA 331-7KB01 - Resistance thermometer Pt100 Standard, Ni100 ±0.5% Pt100 Climate ±0.6% - Thermocouple Type J, K, N, L, E ±0.7% Type T ±1.1%...
Page 104
Manual VIPA System 300V Chapter 6 Analog Input Modules ... continue ... Data for selecting a sensor VIPA 331-7KF01 VIPA 331-7KB01 Connection of the sensors - for measuring voltage possible - for measuring current as 2wire transmitter possible as 4wire transmitter...
Manual VIPA System 300V Chapter 7 Analog Output Modules Chapter 7 Analog Output Modules This chapter contains a description of the structure and the operation of the Outline VIPA analog output modules. The following text describes: • System overview • Safety instructions •...
At the project engineering you should be very careful. With the modules VIPA 332-5HDx0 you can cause a jump in the analog value by means of the switch, independently of the mode of operation of the CPU, as long as the module is power supplied.
Manual VIPA System 300V Chapter 7 Analog Output Modules General For analog signals you should use isolated cables to reduce interference. Cables for analog The cable screening should be grounded at both ends. If there are signals differences in the potential between the cable ends, there may occur a potential compensating current that could disturb the analog signals.
Page 108
Manual VIPA System 300V Chapter 7 Analog Output Modules Connecting loads and actuators Loads at the current output have to be connected at Q and associated Connecting loads ground M of the analog circuit. Please always pay attention to correct at current output polarity.
Manual VIPA System 300V Chapter 7 Analog Output Modules Analog value representation The analog values are only processed by the CPU in binary representation. Analog value Hereby the process signals are transformed into digital format in the analog representation module and passed on to the CPU as word variable.
Simatic 300 > CPU 300 > CPU 315-2 DP. • Link-up your System 300V modules in the plugged-in sequence starting with slot 4. Here the analog output modules of VIPA are to be projected as analog output modules of Siemens in accordance with the following...
Page 111
Manual VIPA System 300V Chapter 7 Analog Output Modules If the module gets parameters, which are not supported by the module, for Parameterization example a current module is to be configured as a voltage module, these during run time parameters are interpreted as wrong parameters and an error is initialized.
Page 112
Manual VIPA System 300V Chapter 7 Analog Output Modules Release diagnostic Please regard as soon as you release the diagnostic interrupt at run time, interrupt the according group diagnostics are just activated during hardware confi- guration. Otherwise no interrupt can be initialized.
Manual VIPA System 300V Chapter 7 Analog Output Modules Diagnostics As soon as an error occurs and activated Group diagnostics, it is Outline protocolled in the diagnostic area that can be evaluated by means of the user application. If the diagnostic interrupt is released at the parameterization, incoming and outgoing error events are signaled by interrupts and monitored on the according analog output module via LED.
Page 114
Manual VIPA System 300V Chapter 7 Analog Output Modules The diagnostics data is stored in the record sets 0 and 1 of the system data Diagnostics data area. As soon as you have activated the diagnostic interrupt release of the parameter area (record set 1, Byte 0), on error record set 0 of the diagnostics data is transferred to the superordinated system.
Page 115
Manual VIPA System 300V Chapter 7 Analog Output Modules The record set 1 contains the 4Byte of record set 0 and additionally 8Byte Diagnosis module specific diagnostic data. Record set 1 The diagnostic bytes have the following content: Byte Bit 7 ... Bit 0 Default 0 ...
Page 116
Manual VIPA System 300V Chapter 7 Analog Output Modules At activated group diagnostics the group error LED (SF) and the according Error indication channel error LED are activated by diagnostic requirement of the modules via LEDs with order no. 332-5Hx01.
Manual VIPA System 300V Chapter 7 Analog Output Modules 332-5Hx01 - AO 2/4x12Bit U/I AO 2x12Bit VIPA 332-5HB01 Order data AO 4x12Bit VIPA 332-5HD01 Depending on the module there are up to 4 analog outputs which functions Description may be parameterized individually.
Page 118
Manual VIPA System 300V Chapter 7 Analog Output Modules Pin assignment Status monitor Circuit diagram Description L+ DC 24V LED (red) AO 4x12Bit Sum error, flashes at missing ext. voltage supply Q0 ... Q3 LED (green) the according channel is activated F0 ...
Page 119
Manual VIPA System 300V Chapter 7 Analog Output Modules Technical data Module name VIPA 332-5HB01 VIPA 332-5HD01 Dimensions and Weight Dimensions (WxHxD) 40x125x120mm Weight 200g Data for Specific Module Number of outputs Length of cable: shielded 200m Programming specifications Output data...
Page 120
Manual VIPA System 300V Chapter 7 Analog Output Modules ... continue Suppression of interference, Limits of Error VIPA 332-5HB01 VIPA 332-5HD01 Crosstalk between outputs > 40dB Operational limit (in the entire temperature range, with reference to the output range) Range...
Page 121
Manual VIPA System 300V Chapter 7 Analog Output Modules ... continue Data for selecting an actuator VIPA 332-5HB01 VIPA 332-5HD01 Output range (nominal value) - Voltage ±10V 0 ... 10V 1 ... 5V - Current ±20mA 0 ... 20mA 4 ... 20mA...
VIPA 332-5HD60: - voltage output 0...10V - deactivated • usable for actuators with an input of 4 ... 20mA (VIPA 332-5HD50) • usable for actuators with an input of 0 ... 10V (VIPA 332-5HD60) • parameterizable diagnostics and diagnostics interrupt •...
Page 123
Manual VIPA System 300V Chapter 7 Analog Output Modules Pin assignment Status monitor Circuit diagram Description L+ DC 24V LED (green) AO 4x12Bit supply voltage is on SM332 Schematic diagram Switch Automatic (A) / Manual (H) Potentiometer Logic HB130E - SM - Rev. 07/44...
Page 124
Manual VIPA System 300V Chapter 7 Analog Output Modules For each channel there is a 2-pole switch with associated potentiometer on Manual operation the front side. The operating mode automatic or manual may be toggled by the switch. At manual operation the module issues the value at the according channel adjusted by the potentiometer.
Page 125
Manual VIPA System 300V Chapter 7 Analog Output Modules Technical data Module name VIPA 332-5HD50 VIPA 332-5HD60 Dimensions and Weight Dimensions (WxHxD in mm) 40x125x120mm Weight 200g Data for Specific Module Number of inputs Length of cable: shielded 200m Programming specifications...
Page 126
Manual VIPA System 300V Chapter 7 Analog Output Modules ... continue technical data 332-5HDx0 Temperature error ±0.01%/K (with reference to the output range) Linearity error ±0.15% (with reference to the input range) Repeatability ±0.05% (in steady state at 25°C, referred to output range) Output ripple;...
Page 127
Manual VIPA System 300V Index Appendix A Index Analog input modules ....6-1 Digital in-/output modules ..... 5-1 331-1KF01 ........ 6-7 323-1BH00 ....... 5-3 Connection ......6-8 323-1BH01 ....... 5-5 Parameterization ....6-10 323-1BL00........ 5-7 Resolution ......6-9 Security hints ......5-2 Technical data....
Page 128
Manual VIPA System 300V Index M.Stich HB130E - SM - Rev. 07/44...
Need help?
Do you have a question about the System 300V and is the answer not in the manual?
Questions and answers