Multi-Function Output Terminal Control; Run Mode Signal; At Frequency Speed Signal; Fault Signal - TECO T-Verter E2 Series Operating Manual

Microprocessor controlled igbt drive inverter motor speed regulator high performance adjustable speed micro drives
Table of Contents

Advertisement

Run/Stop
F_20=4
5. F_19, F_20 = 5: Auto Reset when inverter faults.
F_21: Multi-function output terminal control = 1 ~ 3
1. F_21 = 1: Run mode signal
2. F_22 = 2: At Frequency Speed Signal
3. F_21 = 3: Fault signal
Terminal1 and2 of TM2 are activated at CPF, OL1, OL2, OCS, OCA, OCC, Ocd , Ocb , OVC ,
LVC , OHC.
Hz
F_21=1
Terminal 1 & 2
F_21=2
Terminal 1 & 2
F_22: Reverse Lock-Out
NOTE:
When F_04 is set to 1 (reverse), F_22 cannot be set to 1, in order to properly lockout
a motors direction, F_04 must be set at 0 before setting F_22 to 1.
Hz
off
on
= 0: REV command
= 1: REV command Lock-out
on
on
on
40
off
on
Time