Gree GMV-ND07PLS/A-T(U) Service Manual page 91

Multi variable air conditioners indoor units
Hide thumbs Also See for GMV-ND07PLS/A-T(U):
Table of Contents

Advertisement

GREE
Setting
Setting Content
Code
Indoor environment temperature
P20
value
Corrected value settings of
environment temperature sensor of
P21
IDU (for cooling, dehumidifying,
and air supply)
Corrected value settings of
P22
environment temperature sensor of
IDU (for heating)
Static pressure settings for indoor
P30
fan
P31
High-ceiling installation settings
Capacity adjustment function of
P32
IDU
Repeating validity for time-point
P34
timing
Factory setting recovery for user
P35
functions
Factory setting recovery for
P36
engineering settings
P40
Prevention for heat collection
P42
Project number settings of IDU
P43
Preferential operation settings
One-key project number setting
P44
query for IDU
One-key project number reset for
P45
IDU
Accumulated time clearing for air
P46
filter cleaning
Multi Variable Air Conditioners Indoor Unit
01: temperature sensor of air return vent
02: temperature sensor of wired controller
03: temperature sensor of air return vent for cooling, dehumidifying,
and air supply; temperature sensor of wired controller for heating
04: temperature sensor of wired controller for cooling, dehumidifying,
and air supply; temperature sensor of air return vent for heating and
automatic mode
-15 to 15
-15 to 15
Type 1: 03.04.05.06.07
Type 2: 01.02.03.04.05.06.07.08.09
00: standard-ceiling installation height
01: high-ceiling installation height
-40% to +40%
00: invalid
01: valid
00: invalid
01: factory setting recovery
00: invalid
01: factory setting recovery
00: disabled
10: 10 seconds
20: 20 seconds
30: 30 seconds
40: 40 seconds
50: 50 seconds
60: 60 seconds
1-255
00: no preferential operation
01: preferential operation
00: not displayed
01: displayed
00: invalid
01: project number reset
00: not cleared
01: cleared
85
Setting Value

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents