GREE
Possible reason:
Poor contact between outlet pipe temperature sensor and terminal in mainboard interface
Outlet pipe temperature sensor is abnormal
Detecting circuit is abnormal
1.3.5 "d7" Humidity sensor error
Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error
Possible reason:
Poor contact between humidity sensor and terminal in mainboard interface
Humidity sensor is abnormal
Detecting circuit is abnormal
Multi Variable Air Conditioners Indoor Unit
137