3.1.2 Installation Space
3.1.3 Installation Notice
(1) Installation dimension (refer to the outline dimension in the figure).
(2) Installation foundation.
(3) Make sure the top hanging rod, ceiling and building structure have sufficient strength to
withstand the weight of unit.
(4) Installation site and environment.
1)
Keep the unit from insolation and rainch
2)
Keep the unit from fire, flammable objects, corrosive gap or exhaust gas.
3)
Please reserve ventilation space.
4)
Please reserve sufficient space for maintenance.
5)
Please take proper measures to reduce noise and vibration.
(5) Electrical installation of unit.
All electrical installation must be done by professionals according to national and local laws and
regulations.
The unit must be grounded reliably. Please connect wire according to the wiring diagram on the unit.
3.1.4 Selection of Air Switch and Power Cord
Model
GMV-ND07PLS/A-T(U)
GMV-ND09PLS/A-T(U)
GMV-ND12PLS/A-T(U)
GMV-ND14PLS/A-T(U)
GMV-ND18PLS/A-T(U)
GMV-ND22PLS/A-T(U)
Power Cord Size
208/230V/60Hz
208/230V/60Hz
208/230V/60Hz
208/230V/60Hz
208/230V/60Hz
208/230V/60Hz
95
Multi Variable Air Conditioners Indoor Unit
Air Switch
Minimum Sectional
apacity
Area of Ground Wire
(A)
(mm
/AWG)
2
15
1.0/AWG18
15
1.0/AWG18
15
1.0/AWG18
15
1.0/AWG18
15
1.0/AWG18
15
1.0/AWG18
Unit: mm(inch)
Minimum Sectional
Area of Power Cord
(mm
/AWG)
2
1.0/AWG18
1.0/AWG18
1.0/AWG18
1.0/AWG18
1.0/AWG18
1.0/AWG18