Gree GMV-ND07PLS/A-T(U) Service Manual page 146

Multi variable air conditioners indoor units
Hide thumbs Also See for GMV-ND07PLS/A-T(U):
Table of Contents

Advertisement

GREE
If capacity DIP switch is set to the wrong position, report the error.
Possible reason:
Capacity DIP switch is set to the wrong position
Detecting circuit is abnormal
Troubleshooting:
1.3.10 "dL" Air outlet temperature sensor error
Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error
Possible reason:
Poor contact between air outlet temperature sensor and terminal in mainboard interface
Air outlet temperature sensor is abnormal
Detecting circuit is abnormal
Troubleshooting:
Multi Variable Air Conditioners Indoor Unit