GEM 533 Operating Instructions Manual page 42

Esystep motorized globe valve
Table of Contents

Advertisement

12 Specific data IO-Link (pin 6)
Index name
12.4.30 Analog values
Different analog values can be read out with the Analog values parameter.
Index Sub-
Off-
Access
Index
set
Rights
0x60
1
0
RO
2
16
RO
3
32
RO
Description of parameter values
Index name
Analog values
GEMÜ 533 eSyStep
OPEN / CLOSE (Code AE)
Parameter
Values
Emergency power
0 ... 65.535
Potifail open
0 ... 65.535
Potifail close
0 ... 65.535
Overcurrent out 1
0 ... 65.535
Overcurrent out 2
0 ... 65.535
Length
Index name
12 bits
Analog values
12 bits
12 bits
Parameter
Values
Potentiometer
0 ... 4095
Supply voltage
0 ... 4095
Temperature
0 ... 4095
Number of emergency power cases
Number of times the actuator has moved to its mechanical
stop OPEN.
Number of times the actuator has moved to its mechanical
stop CLOSED.
Number of times output 1 has switched off due to excessive
output current.
Number of times output 2 has switched off due to excessive
output current.
Parameter
Potentiometer
Supply voltage
Temperature
Read out current analog value of the potentiometer.
Read out current analog value of the supply voltage.
Read out current analog value of the temperature sensor.
42 / 55
Description
Type
Values
uint:16
0 ... 4095
uint:16
0 ... 4095
uint:16
0 ... 4095
Description
www.gemu-group.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

533 esystep

Table of Contents