11 Electrical connection
11.3 Overview of available functions – Input and output signals
▶ The factory default setting "Configured for emergency power supply module" is reset to default settings when a reset is
carried out.
▶ When configuring the emergency power module (code A5 / A6), the control of the valve changes. Valve is controlled 1-pole
via digital input 1. Level logic 1 moves the valve OPEN, level logic 0 moves the valve CLOSE.
Digital input 1
Digital input 2
Digital input/output
Digital output
GEMÜ 533 eSyStep
OPEN / CLOSE (Code AE)
Function
Off/Open/Closed/Safe/On/
Initialization
Off/Open/Closed/Safe/On/
Initialization
Open/Closed/Error/Error and
warning/Initialization
Open/Closed/Error/Error and
warning
NOTICE
NOTICE
Control module AE
Default settings
Open
Closed
Open
Closed
20 / 55
Control module A5, A6
Factory default setting
"Configured for emergency
power supply module"
Open
Safe/On
Open
Closed
www.gemu-group.com