22 Introduction and configuration

The interfaces will be set up by the service technician and afterwards they will be ready for opera-
tion. Subsequently, the configuration of the interfaces is described, in order to change the interface
parameters.

22.1 Access levels

The device has 5 access levels; each level has its own password. A lower level has access to all
settings and menus of its own and of the higher levels. The lower the level, the more settings are
available. A lower access level can change the passwords of all other levels.
Access
Description
level
4
Service level; access to all settings for service and maintenance
except some configurations; password changeable
5
Special user level; password automatically generated out of level 6
(password level 6 +1)
6
User level; password changeable
Table 35: Access levels
The password can be entered from any menu by long pressing the Ok-button; alternatively, the
menu item All Settings

22.2 Configuration of communication interfaces

The communication with a higher-level control system is processed through various communication
modules. Up to 3 communication modules can be used simultaneously. Depending on the used
communication module, a reset is required after installation to activate the module in the configura-
tion menu (several resets are necessary while replacing modules); the module type appears auto-
matically, so no need to configure. After login with the password 6975 it`s possible to change
settings for Bacnet IP, Bacnet MSTP, Modbus RTU, LON as following: All settings =>Configu-
ration=>Communication modules=>... .For Modbus IP: All settings=> Configuration=> Con-
troller communication=>IP-Config=>... .
Protocol
Modbus RTU
BACnet MS/TP
BACnet IP
LON
Table 36: Communication protocols
V07-19.0
Password handling can be selected.
Module
Description
POL902
Communication interface for Modbus RTU
POL904
Communication interface for BACnet MS/TP
POL908
Communication interface for BACnet IP
POL906
Communication interface for Lonworks
Key-
Passwor
symbol
d
2 keys
6975
1 key
1001
1 key
1000