Air handling unit
Table of Contents

Advertisement

Description
Return airflow rate – request from air quality control
Supply airflow rate – request from dehumidification
Return airflow rate – request from dehumidification
Supply airflow rate – current setpoint
Return airflow rate – current setpoint
Fan control with speed control:
Supply fan speed for Eco mode
Supply fan speed for Comfort mode
Supply fan speed for Night Setback mode
Return fan speed for Eco mode
Return fan speed for Comfort mode
Return fan speed for Night Setback mode
Maximum supply fan speed from air quality control
Maximum return fan speed from air quality control
Maximum supply fan speed from dehumidification
Maximum return fan speed from dehumidification
Supply fan speed – request from air quality control
Return fan speed – request from air quality control
Supply fan speed – request from dehumidification
Return fan speed – request from dehumidification
Supply fan speed – current set point
Return fan speed – current set point
V07-19.0
(1)
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
R/W
Unit
Modbus
R32
m³/h
H101
R32
m³/h
H103
R32
m³/h
H92
R32
m³/h
H26
R32
m³/h
H28
R/W
0,1 %
H10
R/W
0,1 %
H12
R/W
0,1 %
H18
R/W
0,1 %
H14
R/W
0,1 %
H16
R/W
0,1 %
H20
R/W
0,1 %
H22
R/W
0,1 %
H24
R/W
0,1 %
H30
R/W
0,1 %
H32
R
0,1 %
H100
R
0,1 %
H111
R
0,1 %
H98
R
0,1 %
H94
R
0,1 %
H26
R
0,1 %
H28
BACnet
RetunFlowQAir
SupplyFlowDeHum
RetunFlowDeHum
SupplyFlowSet
ReturnFlowSet
Set_SupplySpeedEco
Set_SupplySpeedCmf
Set_SupplySpeedNht
Set_ReturnSpeedEco
Set_ReturnSpeedCmf
Set_ReturnSpeedNht
Set_SupplySpeedQAirMax
Set_ReturnSpeedQAirMax
Set_SupplySpeedDeHumMax
Set_ReturnSpeedDeHumMax
SupplySpeedQAir
ReturnSpeedQAir
SupplySpeedDeHum
ReturnSpeedDeHum
SupplySpeedSet
ReturnSpeedSet
LON
103/115