Trane CCE-Compact Series Installation Operation & Maintenance page 101

Air handling unit
Table of Contents

Advertisement

Description
Operating mode from HMI
0=Off, 1=Night Setback, 2=Eco, 3=Comfort, 4=Auto
Operating mode from room unit
0=Off, 2=Eco, 3=Comfort, 4=Auto
Operating mode from BMS
0=Off, 1=Night Setback, 2=Eco, 3=Comfort, 4=Auto
Operation mode from hardware contact
0=Auto, 1=Eco, 2=Comfort
Current operating mode
0=Off, 1=Night Setback, 2=Eco, 3=Comfort
Current AHU state / operating mode source
0=No request/off, 1=Start, 2=Configuration changed,
3=Command from HMI, 4=Command from BMS,
5=Command from room unit, 6=Command from scheduler
Operating mode from scheduler
0=-/no request, 1=Off, 2=Night Setback, 3=Eco, 4=Comfort
Winter/Summer-Switching
0=-, 1=Winter, 2=Summer
Ventilatorregelung:
Smoke fan mode
0=Supply/Return, 1=Supply, 2=Return
Fireman fan mode
0=Supply/Return, 1=Supply, 2=Return
Fan start delay (open dampers)
Fan shut down delay electric battery
V07-19.0
R/W
Unit
Modbus
R
0..4
H1
R
0..4
H2
R/W
0..4
H3
R
0..2
H4
R
0..3
H5
R
0..6
H6
R
0..4
H7
R/W
0..2
H224
R/W
0..2
H83
R/W
0..2
H84
R/W
0.1 s
H88
R/W
0.1 s
H89
BACnet
Opmode_HMI
Opmode_RoomUnit
Set_Opmode_BMS
Opmode_HWcontact
Opmode_act
Opmode_Unitstate
Opmode_Scheduler
Set_BMS_WinSum
Set_SmokeFanMode
Set_FiremanFanMode
Set_DmpOpenDelay
Set_FanShutDownDelay
LON
nviOpMode
nvoOpMode
101/115