Warranty - Siemens Acvatix SAS Series Basic Documentation

Table of Contents

Advertisement

L/P-diagram for
AC/DC 24 V
Note
Formulas for wire
lengths
Note
14 / 60
Siemens
Smart Infrastructure
The following diagram can be used to determine the cable lengths and wire cross-
sectional areas.
Permissible cable length L as a function of power P and cross-sectional area of wire as a parameter
P is the decisive power consumption of all actuators connected in parallel. When
operating on AC 24 V, power consumption is in VA; when operating on DC 24 V,
in W.
Operating voltage
AC 230 V
AC 24 V
A
Cross-sectional area of wire in mm
L
Permissible wire length in m
P
Power consumption in VA (AC) or W (DC) (see actuator's rating plate)
I(DC)
DC current part (in A) on G0 wire
2.10

Warranty

The engineering data specified in chapter 2.5 Equipment combinations (page 10)
are only guaranteed in connection with the Siemens valves listed. Siemens rejects
any and all warranties in the event that third-party products are used.
When using the actuators in connection with valves of other manufacture, correct
functioning must be ensured by the user, and Siemens will assume no
responsibility.
Actuators SAS.., SAT.. for valves
Engineering
Power P
Permissible voltage drop / wire
2 % of AC 230 V
4 % of AC 24 V
1 % of DC 10 V
2
Formula for wire length
1313 ·
A
L = 46 ·
[m]
P
1313 ·
A
[m]
L =
P
5.47 ·
A
[m]
L =
I
(DC)
CE1P4041en
2019-04-09

Hide quick links: