Positioning Signal And Flow Characteristic Selection - Siemens Acvatix SAS Series Basic Documentation

Table of Contents

Advertisement

DIL switches
Note
Actuator SAT..
Actuator SAS..
Y, Z
Positioning signal
H
Stroke
Volumetric flow
Heat transfer capacity
32 / 60
Siemens
Smart Infrastructure
4.2.1

Positioning signal and flow characteristic selection

Positioning signal
"Y"
ON
DC 4...20 mA
OFF
ON
DC 0...10 V
OFF
1)
Factory setting: All DIL switches set to OFF
Factory setting SAS..:
· Characteristic curve : log = Equal percentage (switch at "OFF")
· Positioning signal: DC 0...10 V (switch at "OFF")
Factory setting SAT..:
· Characteristic curve: lin = linear (switch at "ON")
· Positioning signal: DC 0...10 V (switch at "OFF")
Flow characteristic
Valve VVG55.. / VVG549..
Valve VVG44.. / VXG44..
Actuators SAS.., SAT.. for valves
Functions and control
Position
feedback "U"
lin =
DC 0...10 V
linear
log =
DC 0...10 V
equal-
percentage
Valve & actuator combined
Valve & actuator combined
Flow characteristic
Valve & actuator & heat
exchanger combined
Valve & actuator & heat
exchanger combined
CE1P4041en