Parameters And Function Description - Siemens Acvatix SAS Series Basic Documentation

Table of Contents

Advertisement

Siemens
Smart Infrastructure
4.3.5

Parameters and function description

Reg.
Name
Process values
1
Setpoint
2
Forced control
3
Actual value
position
256
Command
Parameters
259
Op mode
260
MinPosition
261
MaxPosition
262
Actuator runtime
263
Positioning signal
characteristic
between Y and U
264
Tolerance
blockade
monitoring
513
Backup mode
514
Backup position
515
Backup timeout
516
Startup setpoint
764
Modbus address
765
Baud rate
766
Transmission
format
767
Bus termination
768
Bus config.
command
769
Status
Actuators SAS.., SAT.. for valves
Functions and control
R/W
Unit
Scaling
RW
%
0.01
RW
--
--
R
%
0.01
RW
--
RW
--
--
RW
%
0.01
RW
%
0.01
R
s
1
RW
--
--
RW
%
0.01
RW
--
--
RW
%
0.01
RW
s
1
RW
%
0.01
RW
--
--
RW
--
--
RW
--
--
RW
--
--
RW
--
--
--
--
R
Range / listing
0..100
0 = Off / 1 = Open / 2 = Close
3 = Stop / 4 = Min / 5 = Max
0..100
0 = Ready / 1 = Adaption / 2 = Self test
3 = Reinitialize / 4 = Remote reset
1 = POS
0..100
0..100
30
0 = Linear (e.g. SAX61../MO + V_G41)
1 = Logarithmic (e.g. SAS61../MO + V_G44)
0..10
0 = Move to backup position
1 = Maintain last position / 2 = Disable
0..100
0..65535
0..100
1..247 / 255 = "unassigned"
0 = auto / 1 = 9600 / 2 = 19200 3 = 38400
4 = 57600 / 5 = 76800 / 6 = 115200
0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2
0 = Off / 1 = On
0 = Ready / 1 = Load / 2 = Reject
See Section, Register 769 "Status"
CE1P4041en
2019-04-09
39 / 60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents