Feeding And Suction Line For Light Oil - Ecoflam MAIOR P 500-1 PRE Operating Instructions Manual

Light oil burners
Table of Contents

Advertisement

EN
INSTALLATION

Feeding and suction line for light oil

SUCTION LINE LENGTHS FOR PIPE SYSTEMS
• Two-pipe siphon feed system
• Two-pipe lift system
WARNING: To calculate the length of the pipework all the straight parts, curves, up and down pipes must be taken into consideration.
The static suction height is the distance between the standing valve and the axis of the burner pump.
Negative pressure must not exceed 0,45 bar; if negative pressure is greater pump operation may become faulty, leading to an increase
in mechanical noise and perhaps even breakage.
All oil ring installations must comply with the local safety rules existing in the country of installation
The pumps that are used can be installed both into single-pipe and
double-pipe systems:
Single-pipe system: a single pipe drives the oil from the tank to the pump's
inlet that deliver the pressurized oil to the nozzle and part of the oil not used
goes back to the pump. With this single pipe the by-pass plug must be
removed and the return port must be sealed with steel plug and washer.
Double-pipe system: this is the default solution from the factory.
The return pipe send the excess oil from the pump to the tank. Depending
on the type of pump used to change from a 1-pipe system to a 2-pipe-
system, insert the by-pass plug (as for ccw-rotation referring to the pump
shaft).
Note for commissioning: during commissioning, the filter, pipelines and
pumps must be pre-filled with fuel oil and vented.
The direction of rotation of the motor should be checked. When
commissioning it must be ensured that pump never run dry.
NOZZLE SELECTION
Please refer to diagram to select Ecoflam recommended nozzle for the
output that is required given the output necessary in the installation.
Regular maintenance is highly recommended.
Nozzle has to be cleaned in petrol or paraffin and if filter or other parts are
defective or
damaged the nozzle must be replaced.
NOZZLE CHART IS AVAILABLE ON APPENDIX PAGE
12
www.ecoflam-burners.com
The burner is equipped with a self-priming pump which is capable of feeding
itself within the limits listed in the table at the side.
H
H
H
TA3
(m)
ø 14 mm
ø 16 mm
3
10
32
2,5
8
28
2
7
25
1,5
6
22
1
5
20
0,5
--
17
0
--
15
-0,5
--
10
-1
--
5
-1,5
--
--
-2
--
--
-2,5
--
--
-3
--
--
-3,5
--
--
-4
--
--
Oil under suction
Oil under pressure
By-passed oil
returned to tank,
or to suction
Intake from Tank
Pressure
adjustment
PIPE LENGTH (m)
ø 20 mm
ø 20 mm
115
65
110
60
100
55
95
50
85
45
75
40
65
35
55
28
45
22
37
12
30
7
22
--
9
--
--
--
--
--
SUNTEC TA
Vacuum or
Pressure
inlet pressure
gauge port
gauge port
By-pass
plug
inserted
TWO PIPE
Return
INSTALLATION
Intake from Tank
By-pass
plug
removed
ONE PIPE
Return
INSTALLATION
plugged
420010813300
TA4
ø 30 mm
150
150
150
150
150
150
150
150
150
150
150
150
123
78
38
To nozzle

Advertisement

Table of Contents
loading

This manual is also suitable for:

Maior p 600-1 pre

Table of Contents