Advertisement

Quick Links

PROCESS AUTOMATION
MANUAL
Functional Safety
Switch Amplifier
KFD2-SOT3-Ex*(.LB)(.IO)(-Y1),
KFD2-ST3-Ex*(.LB)
ISO9001
2

Advertisement

Table of Contents
loading

Summary of Contents for Pepperl+Fuchs KFD2-SOT3-Ex

  • Page 1 PROCESS AUTOMATION MANUAL Functional Safety Switch Amplifier KFD2-SOT3-Ex*(.LB)(.IO)(-Y1), KFD2-ST3-Ex*(.LB) ISO9001...
  • Page 2 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent...
  • Page 3: Table Of Contents

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Content 1 Introduction........4 1.1 Contents .
  • Page 4: Introduction

    Additionally, the following parts may belong to the documentation, if applicable: • EC-type of examination • EU declaration of conformity • Attestation of conformity • Certificates • Control drawings • FMEDA report • Assessment report • Additional documents For more information about functional safety products from Pepperl+Fuchs see www.pepperl-fuchs.com/sil.
  • Page 5: Safety Information

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Introduction Safety Information Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator. Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product.
  • Page 6 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Introduction Depending on the risk level, the warning messages are displayed in descending order as follows: Danger! This symbol indicates an imminent danger. Non-observance will result in personal injury or death. Warning! This symbol indicates a possible fault or danger.
  • Page 7: Product Description

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Product Description Product Description Function General This isolated barrier is used for intrinsic safety applications. The device transfers digital signals (NAMUR sensors or dry contacts) from a hazardous area to a safe area. Via switches the mode of operation can be reversed and the line fault detection can be switched off.
  • Page 8: Interfaces

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Product Description Interfaces The device has the following interfaces: • Safety relevant interfaces: • KFD2-SOT3-Ex1.LB(.IO), KFD2-ST3-Ex1.LB: input I, output I, output II • KFD2-SOT3-Ex2(.IO)(-Y1), KFD2-ST3-Ex2: input I, input II, output I, output II • Non-safety relevant interfaces: fault indication output and collective error...
  • Page 9: Planning

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Planning Planning System Structure 3.1.1 Low Demand Mode of Operation If there are two control loops, one for the standard operation and another one for the functional safety, then usually the demand rate for the safety loop is assumed to be less than once per year.
  • Page 10: Assumptions

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Planning Assumptions The following assumptions have been made during the FMEDA: • Failure rate based on the Siemens standard SN29500. • Failure rates are constant, wear is not considered. • External power supply failure rates are not included.
  • Page 11: Safety Function And Safe State

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Planning Safety Function and Safe State Safe State The safe state of output I and output II is the high impedant state. The high impedant state shows an open circuit on the output. Safety Function The safety function has two modes of operation: •...
  • Page 12 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Planning DIP Switch Settings 2-channel Devices Function Mode KFD2-SOT3-Ex2(.IO)(-Y1), KFD2-ST3-Ex2 Mode channel I normal mode S1 position I inverted mode S1 position II Mode channel II normal mode S2 position I inverted mode S2 position II...
  • Page 13: Characteristic Safety Values

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Planning Characteristic Safety Values KFD2-SOT3-Ex*(.LB)(.IO)(-Y1) Parameters acc. to IEC 61508 Characteristic values Assessment type and documentation Full assessment Device type Mode of operation Low demand mode or high demand mode SIL (SC) Safety function Normal/inverted operation 113 FIT ...
  • Page 14 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Planning KFD2-ST3-Ex*(.LB) Parameters acc. to IEC 61508 Characteristic values Assessment type and documentation Full assessment Device type Mode of operation Low demand mode or high demand mode SIL (SC) Safety function Normal/inverted operation 97 FIT ...
  • Page 15: Useful Life Time

    As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer and plant operator can extend the useful lifetime. Our experience has shown that the useful lifetime of a Pepperl+Fuchs product can be higher • if there are no components with reduced life time in the safety loop (for...
  • Page 16: Mounting And Installation

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Mounting and Installation Mounting and Installation Installing the device 1. Observe the safety instructions in the instruction manual. 2. Observe the information in the manual. 3. Observe the requirements for the safety loop. 4. Connect the device only to devices that are suitable for this safety application.
  • Page 17: Operation

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Operation Operation Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device. • Do not bypass the safety function.
  • Page 18 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Operation Check the settings after the configuration by suitable tests. Proof Test Procedure 1. Test each input channel individually. The threshold must be between 1.4 mA and 1.9 mA. The hysteresis must be between 150 A and 250 A.
  • Page 19 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Operation Multimeter KFD2-ST3-Ex1.LB Multimeter (mA) (mA) Multimeter (mA) Fault Supply + 24 V DC Zone 0, 1, 2 Zone 2 Power I supply Supply Div. 1, 2 Div. 2 supply Supply - Figure 5.1 Proof test set-up for KFD2-ST3-Ex1.LB...
  • Page 20 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Operation KFD2-SOT3-Ex1.LB.IO Multimeter (mA) 7+(-) Multimeter (mA) 8-(+) 10+(-) Multimeter (mA) 11-(+) Fault Supply + 24 V DC Zone 0, 1, 2 Zone 2 Power I supply Supply Div. 1, 2 Div. 2 supply Supply - Figure 5.3...
  • Page 21: Maintenance And Repair

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Maintenance and Repair Maintenance and Repair Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device.
  • Page 22: List Of Abbreviations

    Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* List of Abbreviations List of Abbreviations Emergency Shutdown Failure In Time in 10 FMEDA Failure Mode, Effects, and Diagnostics Analysis Probability of safe failure  Probability of dangerous detected failure  Probability of dangerous undetected failure ...
  • Page 23 Functional Safety KFD2-SOT3-Ex*, KFD2-ST3-Ex* Notes...
  • Page 24 PROCESS AUTOMATION – PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621 776-0 E-mail: info@de.pepperl-fuchs.com For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/contact www.pepperl-fuchs.com Subject to modifications Copyright PEPPERL+FUCHS • Printed in Germany DOCT-5021 03/2016...

This manual is also suitable for:

Kfd2-st3-ex

Table of Contents