Functional Safety KCD2-SR-(Ex)*(.LB)(.SP), HiC282*

Operation

5
Operation
Danger!
Danger to life from missing safety function
If the safety loop is put out of service, the safety function is no longer guaranteed.
Do not deactivate the device.
Do not bypass the safety function.
Do not repair, modify, or manipulate the device.
Operating the device
1. Observe the safety instructions in the instruction manual.
2. Observe the information in the manual.
3. Use the device only with devices that are suitable for this safety application.
4. Correct any occurring safe failures within 8 hours. Take measures to maintain the
safety function while the device is being repaired.
5.1

Proof Test

According to IEC/EN 61508-2 a recurring proof test shall be undertaken to reveal
potential dangerous failures that are not detected otherwise.
Check the function of the subsystem at periodic intervals depending on the applied PFD
in accordance with the characteristic safety values. See chapter 3.4.
It is under the responsibility of the plant operator to define the type of proof test and
the interval time period.
Equipment required:
Digital multimeter with an accuracy better than 0.1 %
Use for the proof test of the intrinsic safety side of the device a special digital multimeter
for intrinsically safe circuits.
Intrinsically safe circuits that were operated with non-intrinsically safe circuits may
not be used as intrinsically safe circuits afterwards.
Power supply set to nominal voltage of 24 V DC
18
avg