Conventional Automatic Detectors
5
Technical Data
5.1
Detector and Trim Ring
Detector type
Detection principle
Special features
Individual display
Operating voltage
Current consumption
–
–
–
Response sensitivity:
–
–
Max. monitoring area
Maximum installation
height
Minimum installation
height
Minimum distance to
lamps
Permitted air speed
Permitted operating
temperature
Permitted relative
humidity
Protection class as per
IEC 60529
Dimensions:
–
Bosch Sicherheitssysteme GmbH
FCP-OC 500/FCP-OC 500-P
Standby
Alarm
Malfunction
O unit
Gas unit
Detector without trim
ring
Combination of scattered light
and combustion gas
measurement
–
Contamination detection
–
Drift compensation in
optical and in gas
measuring unit
Two‑color LED: red/green
8.5 to 30 V DC
with FCA-500-EU: 3 mA
with FCA-500-E-EU: 24 mA
47 mA
with FCA-500-EU: 52 mA
with FCA-500-E-EU: 58 mA
< 0.36 dB/m (EN 54-7)
in ppm-range
120 m
2
(note local guidelines)
16 m (note local guidelines)
Out of arm's reach
50 cm
20 m/s
-10 °C to +50 °C
<95 % (non‑condensing)
IP 33
Ø 113 mm x 55 mm (without base)/Ø 113 x 70 mm (with base)
Operation Guide
Technical Data | en
FCP-O 500/FCP-O 500-P
Scattered light measurement
–
Contamination detection
–
Drift compensation in
optical unit
< 0.18 dB/m (EN 54-7)
-
-20 °C to +65 °C
IP 53
2019.11 | 5.0 | F.01U.003.962
25