en | Maintenance and Service
7.2.2

Test instructions for chemical and thermal sensor

Sequential walktest
On the fire panel, in the Walktest menu, select Sequential walktest.
Notice!
i
The test head must remain over the detector until the detector has been triggered. The time
taken to distribute the test aerosol in the test head and therefore the trigger time of the
sensor can be up to 20 seconds.
Simultaneous walktest
Multisensor detectors can be tested simultaneously with the FME-TESTIFIRE multi-stimulus
test tool.
Notice!
i
An alarm message is only displayed on the panel if all sensors are triggered during the
simultaneous walktest. If this does not happen, one of the sensors is faulty.
Testing outside the revision mode
FAP-425-DOTC-R and and FAP-425-DOTCO-R can be triggered outside of the revision mode
only by the following stimuli:
7.3

Diagnostic data

Optical system value (display of the current pollution level)
0 - 230
0 - 350
351 - 450
2023-06 | 07 | F.01U.283.550
All other detector variants: Trigger the thermal sensor with the test device for heat
detectors.
The same test device as for a optical sensor is used to test the CO sensor in the FAP-425-
DOTC-R and FAP-425-DOTCO-R. Exchange the test aerosol with the CO testing gas bottle.
The testing gas must be applied for 1/2 to 1 second for the CO test.
A thermal sensor is tested with the test device for heat detectors.
On the fire panel, in the Walktest menu, select Simultaneous walktest. Observe the
notes in the detector testing device and fire panel operating instructions.
Rise of temperature according to the sensitivity settings A2R, A2S, BR, and BS as defined
by EN 54-5
Simultaneous creation of artificial smoke and CO (by a suitable multi-stimulus test tool,
like FME-TESTIFIRE)
Simultaneous creation of artificial smoke and rise of temperature (by a suitable multi-
stimulus test tool, like FME-TESTIFIRE)
Status: Status of the detector: normal, trouble or alarm.
Type: Detector type.
Physical address: Module where the detector or the detector line is installed.
Logical address: Detector installation address. Example: 10-03 means that the detector is
in zone 10 and has the detector number 3.
Optical analog value IR LED, Optical analog value blue LED
Initial set-up value for a new detector
Normal working range
Slight pollution: Exchange detector soon