Commissioning
Figure 4.9
3.
Switch to the "Network View" tab (1) in the "Devices & Networks" window.
4.
To change the input and output address for the module, double-click the module (2) in the
hardware catalog.
5.
Selecting the Properties > General tab displays the controller properties (3) in the inspector
window below the network view.
6.
If necessary, enter the new address of the module in the input field under PROFIBUS address
> Parameters > Address.
Network view
Note
You must assign unique addresses for data communication between the
module and the read head. If you connect several read heads to one module,
the read heads must have different addresses. This will allow the controller to
allocate the data to the correct module and read heads. If you connect only
one read head to a module, this read head always receives the address 0. You
can connect up to four read heads to a module via an RS-485 cable. Each
read head is supplied with the default address of 0. Details of how to change
the address of the read head can be found in the configuration instructions for
the read head.