Pepperl+Fuchs WCS-PG410 Manual

Pepperl+Fuchs WCS-PG410 Manual

Interface module profibus

Advertisement

Quick Links

WCS-PG410
Interface Module
PROFIBUS
Manual
R

Advertisement

Table of Contents
loading

Summary of Contents for Pepperl+Fuchs WCS-PG410

  • Page 1 WCS-PG410 Interface Module PROFIBUS Manual...
  • Page 2 Phone: +49 621 776 - 0 E-mail: info@de.pepperl-fuchs.com North American Headquarters Pepperl+Fuchs Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 425-3555 E-mail: sales@us.pepperl-fuchs.com Asia Headquarters Pepperl+Fuchs Pte. Ltd. P+F Building 18 Ayer Rajah Crescent Singapore 139942 Phone: +65 6779-9091 E-mail: sales@sg.pepperl-fuchs.com https://www.pepperl-fuchs.com...
  • Page 3: Table Of Contents

    WCS-PG410 Contents Introduction........................ 4 Content of this Document ................4 Target Group, Personnel ................4 Symbols Used ....................4 Product Description ....................6 Use and Application ..................6 Dimensions..................... 6 Design of the Device..................7 Installation........................ 10 Mounting....................... 10 Electrical Connection .................. 11 Dismounting ....................
  • Page 4: Introduction

    WCS-PG410 Introduction Introduction Content of this Document This document contains information required to use the product in the relevant phases of the product life cycle. This may include information on the following: • Product identification • Delivery, transport, and storage •...
  • Page 5: Symbols Used

    WCS-PG410 Introduction Symbols Used This document contains symbols for the identification of warning messages and of informative messages. Warning Messages You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid prop- erty damage.
  • Page 6: Product Description

    WCS-PG410 Product Description Product Description Use and Application The WCS-PG310 interface module acts as an interface between the WCS read head and the PROFIBUS DP input card of the controller. Data is transferred between the WCS read head or WCS read heads and the interface module via the RS-485 interface and from the interface module to the controller via the PROFIBUS DP protocol.
  • Page 7: Design Of The Device

    WCS-PG410 Product Description Design of the Device Device Components Figure 2.2 Interface module overview Slide switch for RS-485 terminator X1: RS-485 interface Mounting bracket X2: Connection for power supply PROFIBUS communication interface Slide switch for PROFIBUS DP terminator Front panel with rotary coding switch and LED status indicator...
  • Page 8 WCS-PG410 Product Description Front Panel WCS-PG410 Modul PROFIBUS Termination Figure 2.3 Front panel overview WCS read head: LED status indicator and rotary coding switch Power/State: The "Power/State" LED lights up green: voltage supply is present. State: The "State" LED is green: Data is being exchanged with the WCS read heads. The four "ErrorNo/Select ID"...
  • Page 9 WCS-PG410 Product Description LED ErrorNo/Select ID Error number Error description LED8 LED4 LED2 LED1 Reserved Hardware error EEPROM error Internal memory error Fieldbus hardware error or incorrect fieldbus Script error Reserved WCS read head communication, RS send buffer overflow WCS read head communication, RS receive...
  • Page 10 WCS-PG410 Product Description PROFIBUS: LED Status Indicator Bus Power: The "Bus Power" LED is green: The LED is connected directly to the electrically isolated supply voltage of the PROFIBUS side. Bus: The "Bus" LED is red: The interface module cannot exchange any data on the PROFIBUS.
  • Page 11: Installation

    WCS-PG410 Installation Installation Mounting Mounting the Modules The module is fastened to a DIN mounting rail with a width of 35 mm using a snap-on fixing method. Figure 3.1 Mounting Hook the module (1) onto the DIN mounting rail (2) from above and press it down until it snaps into place.
  • Page 12: Electrical Connection

    WCS-PG410 Installation Electrical Connection Danger! Device damage due to incorrect installation Incorrect installation of cables and connection lines can endanger the function and the electri- cal safety of the device. • Observe the permissible core cross section of the conductor.
  • Page 13 WCS-PG410 Installation Connecting the Power Supply Connect the operating voltage (10 VDC...30 VDC) to terminals 1 and 2 of the 4-pin plug X2 on the interface module. In addition, note the label on the module. The "Power" LED lights up green.
  • Page 14 WCS-PG410 Installation Preparing for Operation on RS-485 Interface For operation on an RS-485 interface, the terminal on plug X1 must be connected: Connect the read head to the terminal. Use the enclosed jumper to connect the terminals to each other...
  • Page 15: Dismounting

    WCS-PG410 Installation Dismounting Dismounting the modules Use a suitable slot-head screwdriver for dismounting the module. Disconnect all the supply and signal lines. Figure 3.4 Dismounting Insert the screwdriver (2) into the groove of the mounting bracket (3). Press the screwdriver (2) in the specified direction until the lock on the DIN mounting rail (4) opens, see figure.
  • Page 16: Commissioning

    Installation and commissioning must be carried out only by trained personnel in accor- dance with safety regulations. Components To commission the module, you will require the following components: • WCS-PG410 interface module • Cordset from the interface module to the read head • Connector for the PROFIBUS connection to the interface module •...
  • Page 17: Connecting The Wcs Read Head

    WCS-PG410 Commissioning Connecting the WCS Read Head If you connect several WCS read heads to one interface module, the WCS read heads must have different addresses. This will allow the programmable logic controller to allocate the data to the correct WCS read heads. If you connect only one WCS read head to an interface mod- ule, this WCS read head always receives the address 0.
  • Page 18 WCS-PG410 Commissioning Activating the RS-485 Bus Termination If the interface module is operated as the first or last physical device in an RS-485 bus or if you operate one read head on the interface module, a bus termination must be performed on this interface module.
  • Page 19: Connection To The Network

    WCS-PG410 Commissioning Activating the PROFIBUS DP Bus Termination If the interface module is operated as the first or last physical device in the PROFIBUS DP or if you operate one read head on the interface module, this interface module must have a bus ter- minator (220 ).
  • Page 20: Integrating The Interface Module Into The Network

    WCS-PG410 Commissioning Integrating the Interface Module into the Network Warning! Risk of injury due to incorrect configuration An error during the configuration of the device can override the fail-safe function, endangering people and machinery. • Ensure that the device is programmed exclusively by qualified personnel.
  • Page 21 WCS-PG410 Commissioning Figure 4.4 Search GSD file Click the button with the three dots (1), which allows you to search for your GSD file on the storage medium. Select the folder containing the GSD file (2) and click "OK" (3) to confirm your selection.
  • Page 22 Hardware catalogue Open the hardware catalog and browse through the tree structure until you see the icon labeled "276147" (1) (Other field devices > PROFIBUS DP > Gateways > PEPPERL+FUCHS > Pepperl+Fuchs > WCS > WCS-PG310 > Header module > 276147).
  • Page 23 WCS-PG410 Commissioning Figure 4.7 Integrating gsd file Select module "276147" (1) from the hardware catalog and drag this module into the network view (2). The selected module is displayed in the network view window (2). Connect the module to the controller. To do this, move the mouse onto the PROFIBUS interface highlighted in purple for the controller, click the left mouse button, and drag the line shown to the PROFIBUS interface on the module.
  • Page 24 WCS-PG410 Commissioning Setting the Number of Read Heads, Operating Mode, and Addresses You have the option to connect up to four read heads to the interface module. To do this, you must specify the number of modules and their properties in the controller. Several selection options are available in the hardware catalog.
  • Page 25 WCS-PG410 Commissioning Figure 4.9 Network view Switch to the "Network View" tab (1) in the "Devices & Networks" window. To change the input and output address for the module, double-click the module (2) in the hardware catalog. Selecting the Properties > General tab displays the controller properties (3) in the inspector window below the network view.
  • Page 26: Data Format For Modules

    WCS-PG410 Commissioning Data Format for Modules In "only Position" operating mode, 4 bytes are reserved for each WCS reader. Byte 0 Byte 1 Byte 2 Byte 3 Table 4.2 Data format for each connected WCS reader in "only Position" operating mode, reader address = 0...3...
  • Page 27 WCS-PG410 Commissioning Status bits Optical state of Description WCS reader Current position value binary coded in Good P00...P18 WCS reader outside of the code rail, not a Good position value P0...P18=0: WCS reader partly outside the code rail P0=1, P2...P18=0: WCS reader completely...
  • Page 28: Communication With Wcs Read Heads

    WCS-PG410 Communication with WCS read heads Communication with WCS read heads Data Protocols Data protocol 1 Request byte for read head Byte Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0...
  • Page 29 WCS-PG410 Communication with WCS read heads Description of the protocol data Activation of the read head Read head address Read head address 0 Read head address 1 Read head address 2 Read head address 3 Send position value Send diagnosis result...
  • Page 30 WCS-PG410 Communication with WCS read heads Diagnostic bit (DB) Diagnostic bit DB displays the result of the integrated diagnostics of the read head. Function number for read head F0 = 1 (send diagnosis result) State of the read Description head lens...
  • Page 31 WCS-PG410 Communication with WCS read heads OUT message Function number for read head F0 = 0 (send position value) Description State P00...P18 = 0 -> read head is partially outside the code rail P00 = 1, P02...P18 = 0 -> read head is completely...
  • Page 32: Option-E-Extended, Type Wcs3B-Ls2*E*, Rs-485

    WCS-PG410 Communication with WCS read heads Option-E—Extended, Type WCS3B-LS2*E*, RS-485 The read head WCS3-Extended: WCS3B-LS*E* with RS-485 interface is used for routes of more than 314.573 m. In this case, the additional "E" in the type code identifies the extended version for the extending code rail.
  • Page 33 WCS-PG410 Communication with WCS read heads Description of the protocol data Byte 1 A1, A0 Address bits of the read head. Addresses 0 ... 3, binary coding The read head is located in the readable area of the code rail...
  • Page 34 WCS-PG410 Communication with WCS read heads Behavior of the read head in the area of the WCS3 code rail extender (WCS3-CS70-E) The read head retains the last measured end position of the first code rail segment (position = 393203) when traversing the WCS3 code rail extender. The OVL bit is set at the same time. As soon as the first valid position of the second code rail segment is read, the read head switches to the first valid position of the second code rail segment (position = 393318).
  • Page 35: Appendix

    WCS-PG410 Appendix Appendix Cable Routing in the RS-485 Bus The data cables must always form an in-line connection between the first and the last node. This in-line connection must end with a terminator. The RS-485 terminators are integrated in the WCS readers and can be switched on and off with the interface module.
  • Page 36 WCS-PG410 Appendix Reading head Reading head Interface or control (PLC) Figure 6.2 Connection of two reading heads, Version A • Version B: The interface module is located at the beginning of the data line; one WCS reader is located at the end of the data line. Both need the RS-485 terminator. The second WCS reader is connected to the line connection between the interface module and the first WCS reader through a short spur (length <1 m).
  • Page 37 WCS-PG410 Appendix Reading head Spur line (max. 1 m) Reading head Interface or control (PLC) Figure 6.3 Connection of two reading heads, Version B The wiring version used depends on which is best suited for the application. If three or four WCS readers are used on the same interface module, connect these using spurs as shown in variant B.
  • Page 38: Data Cable

    WCS-PG410 Appendix Data Cable A shielded data cable with twisted-pair cores is used for the electrical connection. Pep- perl+Fuchs can supply suitable preassembled M12 single-ended female cordsets () or field- attachable M12 female connectors and data cables. Data Cable WCS-DC* There are two types of data cable available: •...
  • Page 39 WCS-PG410 Appendix Cable Length For the RS-485 data transfer path, a four-wire, shielded, twisted pair data cable must be used. One core pair is used for the supply voltage, and one pair for the RS-485 data connection. The maximum length of the cable depends on the capacitance of the data cable—core-core—for data transfer, and on the cross section of the cables for voltage supply to the read heads.
  • Page 40 WCS-PG410 Appendix Cable Overview The cable types listed below represent a selection of the types available from Pepperl+Fuchs. You can find additional cable types on our website. Note For customizable cables, observe the cable length restrictions specified by the interface specifications.
  • Page 41 Pepperl+Fuchs Quality Download our latest policy here: www.pepperl-fuchs.com/quality www.pepperl-fuchs.com © Pepperl+Fuchs · Subject to modifications Printed in Germany / DOCT-6499...