Pepperl+Fuchs WCS-PG410 Manual page 10

Interface module profibus
Table of Contents

Advertisement

WCS-PG410
Product Description
PROFIBUS: LED Status Indicator
Bus Power:
The "Bus Power" LED is green: The LED is connected directly to the electrically isolated supply
voltage of the PROFIBUS side.
Bus:
The "Bus" LED is red: The interface module cannot exchange any data on the PROFIBUS.
Bus State:
"BusState" LED
Lights up green
Flashes red/green
Lights up red
Flashes green
ID High and ID Low Rotary Coding Switches
You can set the PROFIBUS address using the two ID High and ID Low rotary switches. The dig-
its selected via the two rotary switches together form the PROFIBUS address in hexadecimal
format.
Example: To set the address 19 (= 13h), set the ID High rotary switch to position "1" and the ID
Low rotary switch to position "3."
10
PROFIBUS DP interface state
Data exchange on the PROFIBUS
Interface module is waiting for PROFIBUS parameter data
Error on the PROFIBUS
Interface module is waiting for configuration data