K3MA-L
Temperature Input Shift
Input shift equivalent to the setting value supported for all points
within the sensor measurement range.
Parameter
@EP
È to 
Temperature
Before shift
Temperature input
shift value
Parameter Initialization
This function returns all of the parameters to their initial values.
Parameter
Setting
@E@Q
F77
FE
Use this to reset the K3MA-L after returning it to its factory-set
condition.
Average Processing
Average processing stabilizes displayed values to minimize flicker
by averaging the fluctuating input signals. Average processing
can be performed for the measurement values in either of four
steps (OFF, 2 times, 4 times, or 8 times).
This is useful for ignoring rapid fluctuations, e.g., eliminating spike
noise.
Hysteresis (Comparative Output Models Only)
The hysteresis of comparative outputs can be set to prevent chat-
tering in the output when the measurement value fluctuates finely
near the OUT value.
Upper limit (high acting)
Set value
Measurement value
ON
Output
OFF
6
Setting
After shift
Input
Meaning
---
Initializes all param-
eters.
Hysteresis
Changing the Display Color
The color of the value displayed can be set to either red or green.
For comparative output models, the display color can be set to
change from green to red, or from red to green, according to the
status of the comparison criterion.
OUT1 value
192.0
Display Auto-return Time
This function automatically returns the display to the operation
level's current value if no keys are pressed for a preset time
(called the display auto-return time).
Move-to-Protect-Level Time
The time required to shift to the protect level can be set as
desired.
MAX/MIN Display
The maximum and minimum measurement (display) values from
the time the power is turned ON until the current time can be
stored and displayed. This is useful, for example, when measur-
ing the maximum value.
MAX/MIN
LEVEL
MODE
SHIFT
UP
Max
MAX/MIN
LEVEL
MODE
SHIFT
UP
Min
MAX/MIN
LEVEL
MODE
SHIFT
UP
K3MA-L
Red
258.9
Green
Current value
MAX/MIN
MAX value
MAX/MIN
MIN value
MAX/MIN

Advertisement