Pre-installation Instructions

1. Read all instructions before installing UV lamp kit.
2. Avoid touching the lamp with bare hands as skin oils can ac-
celerate future glass soiling and degrade the lamp performance.
Wipe the lamp with a clean cloth and rubbing alcohol or glass
cleaner after handling.
2. Disconnect all power to the air handler.
!

HAZARDOUS VOLTAGE!

may be present. Disconnect all electrical power, including
remote disconnects, before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be inadver-
tently energized. Failure to disconnect power before servic-
ing could result in death or serious injury.
IMPORTANT: The Right side lamp bracket must be installed before
installing the ballast assembly.
IMPORTANT: The lamp brackets and the ballast assembly are provided
with aggressive adhesive on back. The adhesive has a peel-off liner.
Do not remove the liner until these items have been placed into unit and
proper mounting locations within the unit have been confirmed.
IMPORTANT: The two lamp brackets are not symmetrical. One is
marked Right and the other is marked Left. These markings apply to an
air handler in the vertical upflow configuration (with V-shaped coil orien-
tation). It is very important that the right side and left side brackets are
placed on the proper side so that UV light is directed toward the center
of the coil. Further references to left and right side brackets, top, and bot-
tom in this document assume upflow air handler configuration. For other
configurations see the illustration on page 4 for proper bracket location.
NOTE: Use isopropyl alcohol to thoroughly clean and dry the surfaces
of the inside coil compartment wall in the areas where the lamp brackets
and ballast assembly will be permanently mounted.
NOTE: For new air handler installations, if a UV lamp kit is installed, it
is recommended to remove the coil and install the lamp brackets before
installing the air handler.
18-GJ11D1-2
WARNING
Multiple power sources
End views
(Front of unit)
Left
Right
3