Maintenance - Trane BAYUVCLK001 Installer's Manual

Ultraviolet (uv-c) lamp kit for 2-5 ton air handlers
Table of Contents

Advertisement

Maintenance

IMPORTANT: A UV lamp's characteristic blue glow remains long after
its output drops below an effective level and is not a reliable indicator
of the need for replacement. Contact your dealer to order and install
replacement lamps. To maintain peak efficiency, replace bulb every two
years of operation.
IMPORTANT: Use a clean dry cloth (not bare hands) or clean the lamp
with alcohol or window cleaner after handling.
IMPORTANT: Contact your Dealer for cleaning and maintenance.
!
HAZARDOUS VAPORS!
appropriate respirator should be considered to prevent in-
halation of mercury vapors. Failure to use a respirator could
result in death or serious injury
!
BROKEN GLASS!
broken. Always use gloves and eye protection when handling
these bulbs. Failure to handle bulbs properly may result in
minor to moderate injury.
UV Lamp Replacement
1.
Disconnect all electrical power to the unit.
2.
Open the coil panel.
3.
Cut the cable tie and remove the plug from the lamp.
4.
Wearing soft cloth gloves and safety glasses, use two
hands and firmly grasp the lamp at nearest end.
5.
Slide the lamp and reflector shield out of the unit.
6.
Remove the reflector from lamp.
7.
Snap the reflector on the new lamp.
8.
Install the new lamp.
9.
Place the plug on the lamp.
10.
Replace the coil panel.
Cleaning the UV Lamps
1. Disconnect all electrical power to the unit.
2. Open the coil panel.
3. Cut the cable tie and remove the plug from the lamp.
4. Wearing soft cloth gloves and safety glasses, use two hands
and firmly grasp the lamp at nearest end.
5. Remove the lamp and reflector from the lamp bracket and
slide the lamp out of the unit.
6. Remove the reflector from the lamp.
7. Wipe the lamp with a clean cloth and rubbing alcohol or
glass cleaner. Avoid touching the lamp with bare hands as skin
oils can accelerate future glass soiling and degrade the lamp
performance.
8. Replace the reflector on the lamp.
9. Reinstall the lamp.
10. Replace the plug on the lamp.
11. Replace the coil panel.
14
WARNING
If UV bulbs are broken, an
CAUTION
Bulbs are fragile and can be easily
IMPORTANT: The lamp must remain clean for optimal performance.
IMPORTANT: UV lamps contain mercury, which is a regulated hazard-
ous waste. Disposal of these lamps is subject to state and federal regu-
lations. Although regulations vary from state to state, disposal require-
ments for UV lamps typically conform to those for fluorescent bulbs. The
Association of Lighting and Mercury Recyclers (ALMR) is a nonprofit,
educational, and informative source on mercury recycling and disposal.
To learn about individual state recycling programs, visit their web site at
http://www.almr.org/index.htm.
IMPORTANT: The lamp is held in place by a metal reflector
that is slightly elliptical. You may need to rotate the lamp
when sliding it into the bracket. The lamp will slide in easily
once properly aligned.
IMPORTANT: The lamp is held in place by a metal reflector
that is slightly elliptical. You may need to rotate the lamp
when sliding it into the bracket. The lamp will slide in easily
once properly aligned.
18-GJ11D1-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents